4.9.2.7. Service 8: change user parameters of DP slave<br />

Use this service to overwrite the DP slave's user parameters.<br />

Parameter field<br />

Byte<br />

Parameter<br />

0<br />

B yte 1 Error#<br />

Input<br />

Descriptio n<br />

Service<br />

8 Specifies the service<br />

0 No error<br />

1 Parameter error<br />

7 Internal error<br />

B yte 2 Station#<br />

0...99<br />

Number of DP slave<br />

Byte<br />

3 Length<br />

1...237<br />

Length of user parameter field<br />

Byte<br />

4 U ser_Prm<br />

? Start of user parameter field<br />

User parameter field<br />

The field starts with byte 3 and ends after the length set in<br />

byte 3. For details of this and other entries please refer to<br />

the technical documentation of the relevant device.<br />

What else?<br />

The master does not automatically send the new user parameters<br />

to the DP slave. Proceed as follows to start parameter<br />

transfer:<br />

-- Deactivate the DP slave (service 7)<br />

-- Activate the DP slave (service 7)<br />

Refer to chapter "4.9.2.4. Service 7: activate/deactivate<br />

the DP slave"<br />

Further situations that cause the master to send the user<br />

parameters:<br />

-- After bus failure and subsequent restart<br />

-- After DP slave reset (switch off/on)<br />

-- After master reset (switch off/on)<br />