4.9.2.4. Service 7: activate/deactivate DP slave<br />
<strong>PC</strong> <strong>Control</strong> <strong>645</strong>-<strong>12M</strong> on PROFIBUS<br />
This services allows you to remove specific DP slaves from<br />
(deactivate) or add to (activate) the master's poll list (deactivate).<br />
The master entertains no cyclic data communication with<br />
deactivated slaves. If a slave is re-activated, the master<br />
sends the appropriate device parameter as if it was a new<br />
start-up procedure.<br />
Parameter field<br />
Byte<br />
Parameter<br />
0<br />
B yte 1 Error#<br />
Input<br />
Descriptio n<br />
Service<br />
7 Specifies the service<br />
0 No error<br />
1 Parameter error<br />
7 Internal error<br />
B yte 2 Station#<br />
0...99<br />
Number of DP slave<br />
Byte<br />
3<br />
Action<br />
0...127<br />
Deactivat e<br />
128...255<br />
Activate<br />
The Activate command also enables data communication<br />
even if the relevant slave has been defined to be<br />
"passive" at start-up (see chapter "4.9.2.3.1. Choosing a<br />
station and group").<br />
4 - 53