4.5.3.2. PEaxx.yy: DP slave status messages<br />
<strong>PC</strong> <strong>Control</strong> <strong>645</strong>-<strong>12M</strong> used as PLC<br />
Operand range PEa00.00 to PEa07.13 contains the DP<br />
slave status messages as stored in the master and referenced<br />
by the station address.<br />
PEaxx.yy = slave station address xx*16 + yy:<br />
Operand DP slave address<br />
PEa00.00 0<br />
PEa00.01 1<br />
PEa00.02 2<br />
etc.<br />
The status shown is bit-coded. If a bit is set (= 1) the described<br />
status is active:<br />
Bit<br />
7<br />
6<br />
5<br />
Status<br />
System diagnosis. The master's slave parameter record contains<br />
diagnostic data for this slave. Possible causes:<br />
a: Master has found a local failure<br />
b: Slave has sent diagnostic data<br />
c: Slave did not explicitly cleared extended diagnostic data<br />
Data transfer. Master an DP slave exchanged a valid data frame within<br />
the set Date <strong>Control</strong> Time.<br />
Telegram buffer overflow. Slave responded by sending a longer frame<br />
than expected. Not enough buffer memory for telegram data. Possible<br />
cause: The entry for Max_Diag_Data_Len in this SP slave's GSD file is<br />
not identical with the length of the frame that was actually sent.<br />
4...0<br />
not used<br />
4 - 25