4.5.3.2. PEaxx.yy: DP slave status messages<br />

<strong>PC</strong> <strong>Control</strong> <strong>645</strong>-<strong>12M</strong> used as PLC<br />

Operand range PEa00.00 to PEa07.13 contains the DP<br />

slave status messages as stored in the master and referenced<br />

by the station address.<br />

PEaxx.yy = slave station address xx*16 + yy:<br />

Operand DP slave address<br />

PEa00.00 0<br />

PEa00.01 1<br />

PEa00.02 2<br />

etc.<br />

The status shown is bit-coded. If a bit is set (= 1) the described<br />

status is active:<br />

Bit<br />

7<br />

6<br />

5<br />

Status<br />

System diagnosis. The master's slave parameter record contains<br />

diagnostic data for this slave. Possible causes:<br />

a: Master has found a local failure<br />

b: Slave has sent diagnostic data<br />

c: Slave did not explicitly cleared extended diagnostic data<br />

Data transfer. Master an DP slave exchanged a valid data frame within<br />

the set Date <strong>Control</strong> Time.<br />

Telegram buffer overflow. Slave responded by sending a longer frame<br />

than expected. Not enough buffer memory for telegram data. Possible<br />

cause: The entry for Max_Diag_Data_Len in this SP slave's GSD file is<br />

not identical with the length of the frame that was actually sent.<br />

4...0<br />

not used<br />

4 - 25