4.3. Memory settings<br />
<strong>PC</strong> <strong>Control</strong> <strong>645</strong>-<strong>12M</strong> used as PLC<br />
Apart from the operands (see ch. "4.5. Operands") the following<br />
memory types and capacities are available to the<br />
user:<br />
-- flash EPROM, 320 kbyte<br />
for: program and permanent data<br />
-- RAM, 112 kbyte<br />
for: variable data<br />
The memory space is divided up by use of the corresponding<br />
KUBES programming software functions.<br />
Prerequisites:<br />
-- open project<br />
-- KUBES online<br />
-- PLC stop (options "Stop" or "Stop and reset")<br />
While in online mode, choose option "Online settings"<br />
from the "PLC" menu. The following dialogue is displayed:<br />
program<br />
range<br />
distribution memory type size/bank address range<br />
banks 0...4 flash EPROM 64 kbyte $0...FFFF<br />
bank 5 RAM 64 kbyte $0...FFFF<br />
bank 6 RAM 48 kbyte $0...BFFF<br />
The memory distribution in the illustration above is shown<br />
without data memory. Read the next page to learn how to<br />
reserve data memory.<br />
4 - 13