PROFIBUS hardware installation<br />

B. PROFIBUS hardware installation<br />

B.1. PROFIBUS cable<br />

PROFIBUS standard EN 50 170, PROFIBUS, specifies two<br />

admissible cables to be used for the PROFIBUS-FMS and<br />

PROFIBUS-DP protocols.<br />

Both cable types are discussed below. We recommend using<br />

cable type A because it has advanced properties.<br />

B.1.1. Cable type A<br />

Cable type A recommends itself for high transfer speeds ( ><br />

500 kBaud).<br />

Technical data<br />

-- Char. impedance: 135...165 W<br />

(measuring frequency: 3 to 20 MHz)<br />

-- Cable capacity: < 30 pF per meter<br />

-- Wire diameter: > 0.34 mm², complying with AWG<br />

22<br />

-- Cable type: twisted pair,<br />

1 x 2-, 2 x 2- or 1 x 4-wire<br />

-- Loop resistance: < 110 W per km<br />

-- Signal attenuation: max. 9 dB across the entire length<br />

of the line section<br />

-- Shielding: copper mesh shield or mesh/foil<br />

shield<br />

B.1.1.1. Transfer speed and cable length<br />

Baud rate<br />

9.6<br />

19.<br />

2 93.75<br />

187.<br />

5 500<br />

1500<br />

3000<br />

6000<br />

12000<br />

[kbit/s]<br />

Cable<br />

1200<br />

1200<br />

1200<br />

1000<br />

400<br />

200<br />

100<br />

100<br />

100<br />

length [m]<br />

See next page for information on branch lines<br />