PC Control / Profi Control 645-12M Instruction Manual pdf - Kuhnke
PC Control / Profi Control 645-12M Instruction Manual pdf - Kuhnke PC Control / Profi Control 645-12M Instruction Manual pdf - Kuhnke
PLC error and failure handling Legend for the failures/errors summary Error byte "ERR00.00" The number of the error/failure is written into an error byte (ERR00.00) so that it can be analysed in the user program: Example: L ERR00.00 C8T1 O00.00 ;binary display to 8 outputs Interrupt module [no.] The error/failure triggers an interrupt (IRQ). This causes the monitor program to immediately call up the assigned interrupt module. In the following sections, various types of failures/errors are described and suggested reactions are explained. 4 - 70
4.10.2. Undervoltage (supply, failure no. 2) PC Control 645-12M used as PLC 4.10.2.1. Without external supply The PC supplies PC Control 645-12M with 5 V. If the voltage supply falls below 4.7 V, PC Control 645-12M immediately triggers a RESET. All unbuffered data will get lost. There will be no error message or failure indication. 4.10.2.2. With external supply 1st stage This monitoring function is only enabled while the PC is off and if the external supply fails. Supply voltage: 24 V DC -20%/+25% There is a two-stage reaction by the built-in voltage monitoring function to the falling below certain limiting values: Cause Reaction Indication Supply voltage c. < 19 V -- interrupt module no. 17 will be activated -- the program run will not be interrupted as yet Buffered operands (markers, timers, counters) may be involuntarily reset if the user program is continued to be processed at this stage. This could be caused by decentralised inputs that might detect a 0 signal due to the undervoltage condition. -- LED "failure" flashes (if exists) -- error byte "ERR00.00" is set to 2 4 - 71
- Page 57 and 58: 4.5.2. External operands as process
- Page 59 and 60: PC Control 645-12M used as PLC 4.5.
- Page 61 and 62: 4.5.3.1. Status of PROFIBUS master
- Page 63 and 64: 4.5.3.2. PEaxx.yy: DP slave status
- Page 65 and 66: 4.6. Summary of commands PC Control
- Page 67 and 68: PC Control 645-12M used as PLC 4.6.
- Page 69 and 70: PC Control 645-12M used as PLC 4.6.
- Page 71 and 72: PC Control 645-12M used as PLC 4.6.
- Page 73 and 74: 4.6.4. Shift and rotation commands
- Page 75 and 76: PC Control 645-12M used as PLC 4.6.
- Page 77 and 78: PC Control 645-12M used as PLC 4.6.
- Page 79 and 80: 4.7. Types of operands PC Control 6
- Page 81 and 82: PC Control 645-12M used as PLC 4.8.
- Page 83 and 84: PC Control 645-12M on PROFIBUS 4.9.
- Page 85 and 86: PC Control 645-12M on PROFIBUS PROF
- Page 87 and 88: PC Control 645-12M on PROFIBUS 4.9.
- Page 89 and 90: 4.9.2.3.1. Choosing a station and g
- Page 91 and 92: 4.9.2.4. Service 7: activate/deacti
- Page 93 and 94: 4.9.2.6. Service 6: synchronise DP
- Page 95 and 96: PC Control 645-12M on PROFIBUS 4.9.
- Page 97 and 98: PC Control 645-12M on PROFIBUS ====
- Page 99 and 100: PC Control 645-12M on PROFIBUS ====
- Page 101 and 102: PC Control 645-12M on PROFIBUS ====
- Page 103 and 104: PC Control 645-12M on PROFIBUS ====
- Page 105 and 106: PC Control 645-12M on PROFIBUS ====
- Page 107: PC Control 645-12M used as PLC 4.10
- Page 111 and 112: PC Control 645-12M used as PLC 4.10
- Page 113 and 114: 4.10.5. Hierarchy error (failure #9
- Page 115 and 116: A. Specifications Specifications A.
- Page 117 and 118: Specifications A.2. Order specifica
- Page 119 and 120: PROFIBUS hardware installation B. P
- Page 121 and 122: PROFIBUS hardware installation B.1.
- Page 123 and 124: PROFIBUS hardware installation B.2.
- Page 125 and 126: PROFIBUS hardware installation B.2.
- Page 127 and 128: PROFIBUS hardware installation Acti
- Page 129 and 130: Index A accumulator 3-9 functional
- Page 131 and 132: Index memory range 3-4 in DOS and W
PLC error and failure handling<br />
Legend for the failures/errors summary<br />
Error byte "ERR00.00"<br />
The number of the error/failure is written into an error byte<br />
(ERR00.00) so that it can be analysed in the user program:<br />
Example: L ERR00.00<br />
C8T1 O00.00 ;binary display to 8 outputs<br />
Interrupt module [no.]<br />
The error/failure triggers an interrupt (IRQ). This causes the<br />
monitor program to immediately call up the assigned interrupt<br />
module.<br />
In the following sections, various types of failures/errors<br />
are described and suggested reactions are explained.<br />
4 - 70