Operation of diagnostic function Check code Indoor unit before after 3 series 4 series Cause of operation Status of air conditioner Condition Judgment and measures P03 P03 Discharge temp. error ∗ Discharge temp. (TD) over specified value was detected. Stop Displayed when error is detected 1. Check refrigerating cycle (Gas leak) 2. Trouble of electronic expansion valve 3. Check discharge temp. sensor (TD). P04 H04 Case thermostat operation ∗ Abnormal overheat of compressor Stop Displayed when error is detected 1. Check case thermostat and connector. 2. Check gas leak, recharge 3. Check full open of service valve. 4. Check PMV (Pulse Motor Valve). 5. Check broken pipe. P05 Power supply voltage error Stop Displayed when error is detected 1. Check power supply voltage. AC198 to 264V P20 High pressure protective operation • During cooling operation, outdoor temp. sensor (TL) detected temperature over specified temp. • During heating operation, indoor temp. sensor (TC, TCJ) detected temperature over specified temp. Stop Displayed when error is detected 1. Check outdoor heat exchanger sensor (TL). 2. Check indoor heat exchanger sensor (TC, TCJ). 3. Check full open of service valve. 4. Check indoor/outdoor fan. 5. Check PMV (Pulse Motor Valve). 6. Check clogging and short circuit of indoor/outdoor heat exchanger. 7. Overcharge of refrigerant. Recharge P22 P22 Outdoor fan system error Stop Displayed when error is detected 1. Check lock of fan motor. 2. Check power supply voltage. AC198 to 264V 3. Check outdoor P.C. board. P26 P26 Short-circuit error of compressor driving element Stop Displayed when error is detected 1. When performing operation while taking-off compressor wire, P26 error occurs. Check control P.C. board. 2. When performing operation while taking-off compressor wire, an error does not occur. (Compressor rare short) P29 P29 Position detection circuit error Stop Displayed when error is detected 1. Check control P.C. board. – 98 –
10-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit) Check code [E01 error] Is inter-unit cable of A and B normal? YES NO Correct inter-unit cable of remote controller Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? NO YES Correct connection of connector. Check circuit wiring. NO Is group control operation? YES Is power of all indoor units turned on? YES NO Check power connection of indoor unit. (Turn on power again.) Is power supplied to remote controller? AB terminal: Approx. DC18V YES NO Check indoor P.C. board (MCC-1570). Defect → Replace Are 2 remote controllers set without master unit? NO YES Correct a master unit/a follower unit. (Remote controller address connector) Check remote controller P.C. board. Defect → Replace [E09 error] Are 2 master units set in 2 remote controllers? NO YES Correct as a master unit and a follower unit. Check remote controller P.C. board. Defect → Replace – 99 –
- Page 47 and 48: Table 7-2-1 Thicknesses of annealed
- Page 49 and 50: 43˚to 45˚ 45˚to 46˚ B A C D Fig
- Page 51 and 52: 1) Be sure to make setting so that
- Page 53 and 54: 7-6. Instructions for Re-use Piping
- Page 55 and 56: Revised 2: Jun., 2008 7-6-6. Handli
- Page 57 and 58: 7-6-8. Recovery method of refrigera
- Page 59 and 60: 8-1-2. Connection of Wireless Remot
- Page 61 and 62: 8-2. Control Specifications No. Ite
- Page 63 and 64: No. Item Outline of specifications
- Page 65 and 66: No. Item Outline of specifications
- Page 67 and 68: No. Item Outline of specifications
- Page 69 and 70: No. Item Outline of specifications
- Page 71 and 72: No. Item Outline of specifications
- Page 73 and 74: No. Item Outline of specifications
- Page 75 and 76: Optional power supply CN309 (Yellow
- Page 77 and 78: - 77 - L-phase power supply lead (B
- Page 79 and 80: 3. Outdoor fan control SP110 SP140
- Page 81 and 82: 7. Current release value shift cont
- Page 83 and 84: 1. Pulse Motor Valve (PMV) control
- Page 85 and 86: 2) Heating fan control The outdoor
- Page 87 and 88: 10-1. Summary of Troubleshooting 1
- Page 89 and 90: 10-2. Troubleshooting 10-2-1. Outli
- Page 91 and 92: 10-2-2. Others (Other than Check Co
- Page 93 and 94: - 93 - Check Code List (Outdoor) Re
- Page 95 and 96: Error mode detected by indoor unit
- Page 97: Error mode detected by outdoor unit
- Page 101 and 102: Revised 2: Jun., 2008 [E18 error] I
- Page 103 and 104: [P10 error] Is connection of float
- Page 105 and 106: [F02 error] Revised 2: Jun., 2008
- Page 107 and 108: [E03 error] (Master indoor unit) [
- Page 109 and 110: Check code Outdoor LED display Che
- Page 111 and 112: Check code Outdoor LED display Che
- Page 113 and 114: Check code [L29] Outdoor LED displa
- Page 115 and 116: Check code Outdoor LED display Che
- Page 117 and 118: Check code Outdoor LED display Che
- Page 119 and 120: Temperature sensor Temperature - Re
- Page 121 and 122: Lamp indication Check code Cause of
- Page 123 and 124: - 123 - Check Code List (Outdoor) R
- Page 125 and 126: Error mode detected by remote contr
- Page 127 and 128: 10-2-9. Diagnostic Procedure for Ea
- Page 129 and 130: [E18 error] Is inter-unit cable of
- Page 131 and 132: [P10 error] Revised 2: Jun., 2008
- Page 133 and 134: [F02 error] Revised 2: Jun., 2008
- Page 135 and 136: [E03 error] (Master indoor unit) [
- Page 137 and 138: Check code [F12] [Suction temp. sen
- Page 139 and 140: Check code [P22] [Fan system error]
- Page 141 and 142: 11. REPLACEMENT OF SERVICE P.C. BOA
- Page 143 and 144: Revised 2: Jun., 2008 Setting 4-way
- Page 145 and 146: Revised 2: Jun., 2008 Table 1. Sett
- Page 147 and 148: 12-1. Indoor Unit 12. SETUP AT LOCA
Operation of diagnostic function<br />
Check code<br />
Indoor unit<br />
before after<br />
3 series 4 series<br />
Cause of operation<br />
Status of<br />
air conditioner<br />
Condition<br />
Judgment and measures<br />
P03<br />
P03<br />
Discharge temp. error<br />
∗ Discharge temp. (TD) over specified<br />
value was detected.<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check refrigerating cycle (Gas leak)<br />
2. Trouble of electronic expansion valve<br />
3. Check discharge temp. sensor (TD).<br />
P04<br />
H04<br />
Case thermostat operation<br />
∗ Abnormal overheat of compressor<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check case thermostat and connector.<br />
2. Check gas leak, recharge<br />
3. Check full open of service valve.<br />
4. Check PMV (Pulse Motor Valve).<br />
5. Check broken pipe.<br />
P05<br />
Power supply voltage error<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check power supply voltage. AC198 to 264V<br />
P20<br />
High pressure protective operation<br />
• During cooling operation, outdoor<br />
temp. sensor (TL) detected<br />
temperature over specified temp.<br />
• During heating operation, indoor<br />
temp. sensor (TC, TCJ) detected<br />
temperature over specified temp.<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check outdoor heat exchanger sensor (TL).<br />
2. Check indoor heat exchanger sensor (TC, TCJ).<br />
3. Check full open of service valve.<br />
4. Check indoor/outdoor fan.<br />
5. Check PMV (Pulse Motor Valve).<br />
6. Check clogging and short circuit of indoor/outdoor heat<br />
exchanger.<br />
7. Overcharge of refrigerant. Recharge<br />
P22<br />
P22<br />
Outdoor fan system error<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check lock of fan motor.<br />
2. Check power supply voltage. AC198 to 264V<br />
3. Check outdoor P.C. board.<br />
P26<br />
P26<br />
Short-circuit error of compressor<br />
driving element<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. When performing operation while taking-off compressor<br />
wire, P26 error occurs. Check control P.C. board.<br />
2. When performing operation while taking-off compressor<br />
wire, an error does not occur. (Compressor rare short)<br />
P29<br />
P29<br />
Position detection circuit error<br />
Stop<br />
Displayed when<br />
error is detected<br />
1. Check control P.C. board.<br />
– 98 –