Remote<br />
controller<br />
indication<br />
F01<br />
F02<br />
F10<br />
F29<br />
P01<br />
P10<br />
P12<br />
P31<br />
—<br />
—<br />
L20<br />
—<br />
Sensor lamp part<br />
Block indication<br />
Operation Timer Ready Flash<br />
¥ ¥ l ALT<br />
¥ ¥ l ALT<br />
¥ ¥ l ALT<br />
¥ ¥ l SIM<br />
l ¥ ¥ ALT<br />
l ¥ ¥ ALT<br />
l ¥ ¥ ALT<br />
¥ l ¥ ALT<br />
By unit with warning No.<br />
—<br />
ALT<br />
¥ ¡ ¥ SIM<br />
—<br />
Representative defective position<br />
Indoor unit Heat exchanger sensor (TCJ) error<br />
Indoor unit Heat exchanger sensor (TC) error<br />
Indoor unit Room temp. sensor (TA) error<br />
Indoor unit Other indoor P.C. board error<br />
Indoor unit Indoor fan error<br />
Indoor unit Overflow detection<br />
Indoor unit Indoor fan error<br />
Other indoor unit error<br />
Error in indoor group<br />
LAN system communication error<br />
LAN system communication error<br />
There are multiple communication adapters.<br />
¡ : Go on, ¥ : Flash, l : Go off<br />
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED<br />
Detection<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Network adapter<br />
Network adapter/<br />
Center<br />
Network adapter/<br />
Center<br />
Network adapter<br />
Explanation of error contents<br />
Open/Short of heat exchanger (TCJ) was detected.<br />
Open/Short of heat exchanger (TC) was detected.<br />
Open/Short of room temp. (TA) was detected.<br />
EEPROM error (Other error may be detected. If no error, automatic address is repeated.<br />
Indoor AC fan error was detected. (Fan thermal relay worked.)<br />
Float switch worked.<br />
Indoor fan error (Over-current / Lock, etc.) was detected.<br />
Other indoor under condition of warning in group. E03/L07/L03/L08 warning<br />
Sub remote controller error in a group<br />
(Details of remote controller are displayed with unit No. Only central control side is displayed.)<br />
Communication error of central control system signal<br />
∗ Is not displayed on the remote controller<br />
Duplicated indoor address of central control system communication<br />
There are multiple communication adapters on remote controller communication line.<br />
Automatic<br />
reset<br />
Operation<br />
continuation<br />
¡ ×<br />
¡ ×<br />
¡ ×<br />
× ×<br />
× ×<br />
× ×<br />
× ×<br />
¡ ×<br />
— —<br />
¡ ¡<br />
¡ ×<br />
¡ ¡<br />