Remote<br />

controller<br />

indication<br />

F01<br />

F02<br />

F10<br />

F29<br />

P01<br />

P10<br />

P12<br />

P31<br />

—<br />

—<br />

L20<br />

—<br />

Sensor lamp part<br />

Block indication<br />

Operation Timer Ready Flash<br />

¥ ¥ l ALT<br />

¥ ¥ l ALT<br />

¥ ¥ l ALT<br />

¥ ¥ l SIM<br />

l ¥ ¥ ALT<br />

l ¥ ¥ ALT<br />

l ¥ ¥ ALT<br />

¥ l ¥ ALT<br />

By unit with warning No.<br />

—<br />

ALT<br />

¥ ¡ ¥ SIM<br />

—<br />

Representative defective position<br />

Indoor unit Heat exchanger sensor (TCJ) error<br />

Indoor unit Heat exchanger sensor (TC) error<br />

Indoor unit Room temp. sensor (TA) error<br />

Indoor unit Other indoor P.C. board error<br />

Indoor unit Indoor fan error<br />

Indoor unit Overflow detection<br />

Indoor unit Indoor fan error<br />

Other indoor unit error<br />

Error in indoor group<br />

LAN system communication error<br />

LAN system communication error<br />

There are multiple communication adapters.<br />

¡ : Go on, ¥ : Flash, l : Go off<br />

ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED<br />

Detection<br />

Indoor<br />

Indoor<br />

Indoor<br />

Indoor<br />

Indoor<br />

Indoor<br />

Indoor<br />

Indoor<br />

Network adapter<br />

Network adapter/<br />

Center<br />

Network adapter/<br />

Center<br />

Network adapter<br />

Explanation of error contents<br />

Open/Short of heat exchanger (TCJ) was detected.<br />

Open/Short of heat exchanger (TC) was detected.<br />

Open/Short of room temp. (TA) was detected.<br />

EEPROM error (Other error may be detected. If no error, automatic address is repeated.<br />

Indoor AC fan error was detected. (Fan thermal relay worked.)<br />

Float switch worked.<br />

Indoor fan error (Over-current / Lock, etc.) was detected.<br />

Other indoor under condition of warning in group. E03/L07/L03/L08 warning<br />

Sub remote controller error in a group<br />

(Details of remote controller are displayed with unit No. Only central control side is displayed.)<br />

Communication error of central control system signal<br />

∗ Is not displayed on the remote controller<br />

Duplicated indoor address of central control system communication<br />

There are multiple communication adapters on remote controller communication line.<br />

Automatic<br />

reset<br />

Operation<br />

continuation<br />

¡ ×<br />

¡ ×<br />

¡ ×<br />

× ×<br />

× ×<br />

× ×<br />

× ×<br />

¡ ×<br />

— —<br />

¡ ¡<br />

¡ ×<br />

¡ ¡<br />

– 94 –