2) Heating fan control<br />

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.<br />

(From Min. W1 to Max. are controlled according to the following table.)<br />

‚ During 3 minutes after start-up, the fan is fixed<br />

with the maximum fan tap corresponding to zone<br />

in the following table.<br />

After then the fan is controlled by temperature of<br />

TE sensor.<br />

ƒ If status, TE > 24°C continues for 5 minutes, the<br />

operation stops.<br />

This status is same to the usual Thermo-OFF<br />

which has no alarm display, and the fan restarts<br />

after 2 minutes and 30 seconds.<br />

This intermittent operation is not abnormal.<br />

„ When the above status ‚ occurs frequently, it is<br />

considered that the filter of suction part of the<br />

indoor unit is stain.<br />

Clean the filter and then restart the operation.<br />

TE [˚C]<br />

24<br />

21<br />

18<br />

15<br />

–2 tap/20 seconds<br />

STOP timer count<br />

–2 tap/20 seconds<br />

–1 tap/20 seconds<br />

rpm hold<br />

+1 tap/20 seconds<br />

Maximum<br />

Temp. range<br />

10°C ≤ TO<br />

5 ≤ TO < 10°C<br />

–5 ≤ TO < 5°C<br />

TO < –5°C<br />

TO error<br />

f < 38.9Hz 38.9Hz ≤ f < 67.6Hz 67.6Hz ≤ f<br />

W7 W8 W9<br />

WA WB WD<br />

WE WF WF<br />

WE WF WF<br />

WE WF WF<br />

5. Coil heating control<br />

1) This control function heats the compressor by turning on the stopped compressor instead of a case heater.<br />

It purposes to prevent slackness of the refrigerant inside of the compressor.<br />

2) As usual, turn on power of the compressor for the specified time before a test run after installation,<br />

otherwise a trouble of the compressor may be caused.<br />

As same as a test run, it is recommended to turn on power of the compressor beforehand when starting<br />

operation after power of the compressor has been interrupted for a long time.<br />

3) Coil heating is controlled by TD and TE sensor.<br />

4) The power is turned off when TD is 30°C or more.<br />

TE [˚C]<br />

0<br />

–1<br />

–6<br />

–7<br />

No power-ON<br />

Continuous ON (L)<br />

Continuous ON (H)<br />

L<br />

H<br />

SP40, SP45<br />

10W and equivalent<br />

30W and equivalent<br />

– 85 –