SUPER DIGITAL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3. Outdoor fan control<br />
SP110<br />
SP140<br />
Up<br />
Down<br />
Revolution frequency allocation of fan taps [rpm]<br />
W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE<br />
200 240 240 260 320 380 480 500 530 610 640 660 720 780<br />
— — 200 280 360 400 500 520 550 630 660 700 740 820<br />
3-1) Cooling fan control<br />
The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency.<br />
The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).<br />
‚ Only for 60 seconds after the operation has started, the maximum fan tap corresponding to the<br />
zone in the following table is fixed and then the fan is controlled by temperature of TL sensor.<br />
TL [˚C]<br />
58<br />
55<br />
WE tap<br />
Temp. range<br />
38°C ≤ TO<br />
20 Hz 20Hz 45Hz<br />
or lower to 45Hz or higher<br />
Min. Max. Min. Max. Min. Max.<br />
W6 WC W8 WC WA WD<br />
+1 tap / 20 sec<br />
Up to the maximum<br />
revolution frequency of each zone<br />
29°C ≤ TO < 38°C<br />
15°C ≤ TO < 29°C<br />
5°C ≤ TO < 15°C<br />
W5 WB W7 WC∗ W9 WC<br />
W4 W8 W6 WA W8 WC<br />
W3 W6 W5 W8 W7 WA<br />
38<br />
35<br />
Revolution frequency hold<br />
–1 tap / 20 sec<br />
Up to the minimum<br />
revolution frequency of each zone<br />
0°C ≤ TO < 5°C<br />
–4°C ≤ TO < 0°C<br />
TO < –4°C<br />
TO error<br />
W2 W4 W4 W6 W5 W8<br />
W2 W3 W3 W5 W4 W6<br />
W1 W2 W1 W4 W2 W6<br />
W1 WC W1 WC W2 WD<br />
3-2) Heating fan control<br />
TE [˚C]<br />
24<br />
21<br />
18<br />
15<br />
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.<br />
(Control from minimum W1 to maximum (according to the following table))<br />
‚ For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in<br />
the following table is fixed and then the fan is controlled by temperature of TE sensor.<br />
–2 taps / 20 sec. (Up to W1)<br />
Stop timer count<br />
–2 taps / 20 sec. (Up to W1)<br />
–1 tap / 20 sec. (Up to W1)<br />
Revolution frequency hold<br />
+1 tap / 20 sec<br />
(Up to the maximum tap of each zone)<br />
* : WB for SP110<br />
ƒ When TE ≥ 24°C continues for 5 minutes, the<br />
compressor stops.<br />
It is the same status as the normal thermostat-<br />
OFF without error display.<br />
The compressor restarts after approx. 2 minutes<br />
30 seconds and this intermittent operation is not<br />
abnormal.<br />
„ In case that the status in item ƒ generates<br />
frequently, stain on filter of the suction part of the<br />
indoor unit is considered.<br />
Clean the filter and then restart the operation.<br />
Object: SP140<br />
Object: SP110<br />
Temp. range<br />
20 Hz 20Hz 45Hz<br />
or lower to 45Hz or higher<br />
Max. Max. Max.<br />
Temp. range<br />
20 Hz 20Hz 45Hz<br />
or lower to 45Hz or higher<br />
Max. Max. Max.<br />
10°C ≤ TO<br />
W7 W8 W9<br />
10°C ≤ TO<br />
W7 W8 W9<br />
5°C ≤ TO < 10°C<br />
W9 WA WB<br />
5°C ≤ TO < 10°C<br />
W9 WA WA<br />
–3°C ≤ TO < 5°C<br />
WB WB WC<br />
–3°C ≤ TO < 5°C<br />
WA WA WB<br />
–10°C ≤ TO < –3°C<br />
WC WC WC<br />
–10°C ≤ TO < –3°C<br />
WB WB WB<br />
TO < –10°C<br />
WD WD WD<br />
TO < –10°C<br />
WD WD WD<br />
TO error<br />
WD WD WD<br />
TO error<br />
WD WD WD<br />
– 79 –