9-2. Outline of Main Controls<br />

<br />

1. PMV (Pulse Motor Valve) control<br />

1) PMV is controlled between 30 and 500 pulsed during operation.<br />

2) In cooling operation, PMV is usually controlled with the temperature difference between TS sensor and<br />

TC sensor aiming 1 to 4K as the target value.<br />

3) In heating operation, PMV is usually controlled with the temperature difference between TS sensor and<br />

TE sensor aiming –1 to 4K as the target value.<br />

4) When the cycle excessively heated in both cooling and heating operation, PMV is controlled by TD<br />

sensor. The target value is usually 91°C in cooling operation and 96°C in heating operation.<br />

REQUIREMENT<br />

A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the<br />

compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance<br />

value or the refrigerating cycle of each sensor after repair and then start the operation.<br />

2. Discharge temperature release control<br />

1) When the discharge temperature did not fall or the discharge temperature rapidly went up by PMV<br />

control, this control lowers the operation frequency. It subdivides the frequency control up to 0.6Hz to<br />

stabilize the cycle.<br />

2) When the discharge temperature detected an abnormal stop zone, the compressor stops and then<br />

restarts after 2 minutes 30 seconds.<br />

The error counting is cleared when the operation continued for 10 minutes. If the error is detected by<br />

4 times without clearing, the error is determined and restarting is not performed.<br />

∗ The cause is considered as excessively little amount of refrigerant, PMV error or clogging of the cycle.<br />

3) For displayed contents of error, confirm on the check code list.<br />

TD [˚C]<br />

111<br />

109<br />

106<br />

103<br />

96<br />

Abnormal stop<br />

Frequency normal down<br />

Frequency slow down<br />

Frequency hold<br />

Frequency slow up<br />

(Up to command)<br />

As command is<br />

– 78 –