Function<br />

Humidifier output (∗)<br />

ntilation output<br />

HA<br />

Option output<br />

Outside error input<br />

AUTO up/down grille<br />

(∗)<br />

Connector No.<br />

CN66<br />

CN32<br />

CN61<br />

CN60<br />

CN80<br />

CN20<br />

Pin No.<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

2<br />

3<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Specifications<br />

DC12V<br />

Output (Open collector)<br />

DC12V<br />

Output (Open collector)<br />

ON/OFF input<br />

0V<br />

Remote controller prohibited input<br />

Operation output (Open collector)<br />

DC12V<br />

Warning output (Open collector)<br />

DC12V<br />

Defrost output (Open collector)<br />

Thermostat ON output (Open collector)<br />

Cooling output (Open collector)<br />

Heating output (Open collector)<br />

Fan output (Open collector)<br />

DC12V<br />

NC<br />

Outside error input<br />

DC12V<br />

Panel operation input<br />

Panel up output (Open collector)<br />

Panel down output (Open collector)<br />

0V<br />

Remarks<br />

Humidifier output is ON when heating operation is performed, when thermostat is on, when the fan is on.<br />

∗ The setting of Humidifier provided + Drain pump ON is performed by short-circuit of CN70 or from the<br />

remote controller. (DN [40] = 0001)<br />

Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop operation<br />

∗ The single operation setting by FAN button on the remote controller is performed on the remote<br />

controller (DN [31] = 0000 → 0001)<br />

HA ON/OFF input (J01: YES/NO=Pulse (At shipment from factory) /Static input selection)<br />

Permission/Prohibition of remote controller operation stop is performed by input.<br />

Operation ON (Answer back of HA)<br />

Warning output ON<br />

ON when outdoor unit is defrosted<br />

ON when real thermostat is on. (Compressor ON)<br />

ON when operation mode is cooling system (COOL, DRY, Cooling/Heating automatic cooling)<br />

ON when operation mode is heating system (HEAT, Cooling/Heating automatic heating)<br />

ON when indoor fan is on. (When air cleaner is used) OFF while clean operation is performed.<br />

Generate the warning code “L30” (continuously for 1 minute) and stop the operation forcibly.<br />

The grille is controlled according to up/down operation from the remote controller.<br />

∗ Setting of automatic up/down grille provided is performed on the remote controller.<br />

(DN [30] = 0000 → 0001)<br />

8-3. Optional Connector Specifications of Indoor P.C. Board<br />

FILTER<br />

Option error /<br />

Humidifier setting (∗)<br />

CN70<br />

1<br />

2<br />

0V<br />

Selection of option error input (Protective operation display of device attached to outside) or Humidifier<br />

setting input (Vaporizing + Drain pump ON)<br />

Humidifier is set at shipment from factory.<br />

∗ Setting of option error input is performed on the remote controller. (DN [2A] = 0002 → 0001)<br />

CHK<br />

Operation check<br />

CN71<br />

1<br />

2<br />

0V<br />

This check is used to check indoor operation. (Performs operation of indoor fan “H”, Louver horizontal<br />

and Drain pump ON without communication with outdoor and remote controller)<br />

DISP<br />

Exhibition mode<br />

CN72<br />

1<br />

2<br />

0V<br />

Communication is available by indoor unit and remote controller only.<br />

EXCT<br />

Demand<br />

CN73<br />

1<br />

2<br />

Demand input<br />

0V<br />

Indoor unit forced thermostat OFF operation<br />

* This option is not provided to oversea models.