Item<br />
Outline of specifications<br />
Remarks<br />
19<br />
DC motor<br />
1) When the fan operation has started, positioning of the<br />
stator and the rotor are performed.<br />
(Moves slightly with tap sound)<br />
2) The motor operates according to the command from the<br />
indoor controller.<br />
Notes)<br />
• When the fan rotates while the air conditioner stops due to<br />
entering of outside air, etc, the air conditioner may operate<br />
while the fan motor stops.<br />
• When a fan lock is found, the air conditioner stops, and an<br />
error is displayed.<br />
Check code [P12]<br />
20<br />
Self-clean operation<br />
(Dry operation):<br />
In case of 4-way<br />
Discharge Cassette<br />
type<br />
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following<br />
three self-clean operations are performed.<br />
Compressor<br />
ON period<br />
0 to 10 min.<br />
10 to 60 min.<br />
60 min. to<br />
Self-clean<br />
operation period<br />
None<br />
1 hour<br />
2 hours<br />
FAN<br />
Fan (UL)<br />
Drain pump<br />
STOP<br />
Louver<br />
Horizontal discharge position<br />
2) During operation of self-clean, lights on the wired<br />
remote controller screen. However the operation lamp<br />
(Green LED) goes off.<br />
3) To stop the self-clean operation, push twice the<br />
[ON/OFF] button on the remote controller continuously.<br />
(Stop the operation as compressor ON time in the table<br />
above: 10 minutes or below.)<br />
4) When the follower unit executes self-clean operation in the<br />
group connection, the segment of is displayed on the<br />
wired remote controller screen via master unit.<br />
∗ If self-clean operation is not used, set invalidity<br />
(does not use) of the self-clean operation by changing<br />
[0001 (At shipment) of Item code (DN) [D3] to [0000].<br />
∗ To erase the display during operation of self-clean,<br />
change Item code [D4] from [0000: Display<br />
(At shipment)] to [0001: Non-display].<br />
On the remote controller<br />
before the wired<br />
remote controller<br />
(RBC-AMT31E),<br />
Self-clean operation<br />
display is not output.<br />
And it is not also on<br />
the wireless remote<br />
controller.<br />
It is recognized as<br />
[STOP] from the<br />
remote monitor side.<br />
21<br />
Save operation<br />
SAVE<br />
1) Turn on button on the remote controller.<br />
SAVE<br />
2) During operation of save operation, lights on the<br />
wired remote controller.<br />
3) During save operation, the current release control is<br />
performed with the restriction ratio set in EEPROM on<br />
the outdoor unit.<br />
SAVE<br />
4) The restriction ratio can be set by keeping button<br />
pushed for 4 seconds or more on the remote controller.<br />
5) When validating the save operation, the next operation<br />
starts with save operation valid because contents are<br />
held even when operation stops, operation mode<br />
changes or power supply is reset.<br />
6) The restriction ratio can be set by changing the setup<br />
data of Item code (DN) [C2] in the range of 50 to 100%<br />
(every 1%, Setting at shipment: 75%).<br />
Operation and display<br />
also are unavailable on<br />
the wired remote<br />
controller RBC-<br />
AMT31E and before.<br />
Carry out setting<br />
operation during stop of<br />
the unit; otherwise the<br />
unit stops operation.<br />
For the setup operation,<br />
refer to “How to<br />
set up contents of<br />
save operation” of<br />
Installation Manual.<br />
– 72 –