27.03.2014 Views

SUPER DIGITAL

SUPER DIGITAL

SUPER DIGITAL

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Revised 2: Jun., 2008<br />

No.<br />

Item<br />

Outline of specifications<br />

Remarks<br />

12<br />

Louver control<br />

(Continued):<br />

In case of 4-way<br />

Discharge<br />

Cassette type<br />

• If there is the locked louver in the unit, [ ] goes on the<br />

remote controller screen.<br />

• While the following controls are performed, the louvers<br />

operate even if executing the louver lock.<br />

Control which ignores lock<br />

Objective louver No.<br />

For the setting<br />

operation, refer to<br />

[How to set louver<br />

lock] of Installation<br />

Manual.<br />

‚<br />

ƒ<br />

„<br />

…<br />

†<br />

Operation stop<br />

When heating operation started<br />

Heating thermo. OFF<br />

During defrost operation<br />

Initialize operation<br />

Self-clean operation<br />

Full-close position<br />

Horizontal discharge position<br />

Horizontal discharge position<br />

Horizontal discharge position<br />

Full-close position<br />

Horizontal discharge position<br />

• The real louver corresponding to the louver No. displayed on the<br />

remote controller screen during setting of louver lock operates<br />

swinging.<br />

It is position check<br />

operation and it<br />

does not link with<br />

the real louver and<br />

air direction setup<br />

(Illustration on the<br />

remote controller<br />

screen).<br />

13<br />

HA control<br />

1) This control is connected to TV control or remote start/stop<br />

I/F, etc, and start/stop are available by HA signal input from<br />

the remote position.<br />

2) This control outputs start/stop status to HA output terminal.<br />

3) I/O specifications conform to JEMA regulations.<br />

4) This control outputs [Operation OFF (STOP) signal] to HA<br />

output terminal while self-cleaning works. However selection of<br />

[Operation ON (Operating) signal] is possible by changing<br />

[0000 (At shipment)] of Item code (DN) [CC] to [0001]. In this<br />

case, if HA is input during self-clean operation during operation<br />

of the air conditioner, the self-clean operation is not performed.<br />

(Unit stops.)<br />

In the group operation,<br />

use this control<br />

by connecting to<br />

either master or<br />

follower indoor unit.<br />

14<br />

Frequency fixed<br />

operation (Test run)<br />

<br />

1) When pushing [CHK] button for 4 seconds or more, [TEST]<br />

is displayed on the display screen and the mode enters in<br />

Test run mode.<br />

2) Push [ON/OFF] button.<br />

3) Using [MODE] button, set the mode to [COOL] or [HEAT].<br />

• Do not use other mode than [COOL]/[HEAT] mode.<br />

• During test run operation, the temperature cannot be<br />

adjusted.<br />

• An error is detected as usual.<br />

• A frequency fixed operation is performed.<br />

4) After the test run, push [ON/OFF] button to stop the operation.<br />

(Display in the display part is same as the procedure in Item 1.)<br />

5) Push [CHK] button to clear the test run mode.<br />

([TEST] display in the display part disappears and the<br />

status returns to the normal stop status.)<br />

Command frequency<br />

is approximately [S7]<br />

15 Filter sign display<br />

(Except wireless<br />

type)<br />

∗ It is provided on<br />

the separately<br />

sold type<br />

TCB-AX21E2.<br />

1) The operation time of the indoor fan is calculated, the filter reset<br />

signal is sent to the remote controller when the specified time<br />

(2500H) has passed, and it is displayed on LCD.<br />

2) When the filter reset signal has been received from the<br />

remote controller, time of the calculation timer is cleared.<br />

In this case, the measurement time is reset if the specified<br />

time has passed, and display on LCD disappears.<br />

[FILTER<br />

] goes on.<br />

– 70 –