No. Item Outline of specifications Remarks 7 Cool air discharge preventive control 1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor. As shown below, the upper limit of the revolution frequency is restricted. However B zone is assumed as C zone for 6 minutes and after when the compressor activated. In defrost operation, the control value of Tc is shifted by 6°C. In D and E zones, the priority is given to air volume selection setup of remote controller. In A zone while thermo is ON, [PRE-HEAT (Heating ready)] is displayed. Tc Tcj (˚C) HH 32 H 30 L 28 UL 26 OFF 20 16 E zone D zone C zone B zone A zone 8 Freeze preventive control (Low temperature release) 1) The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. When [J] zone is detected for 6 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone. In [K] zone, time counting is interrupted and the operation is held. When [ I ] zone is detected, the timer is cleared and the operation returns to the normal operation. If the commanded frequency becomes S0 because the operation continues in [J] zone, the return temperature A is raised from 5°C to 12°C until [ I ] zone is detected and the indoor fan operates with [L] mode. Tcj: Indoor heat exchanger sensor temperature (˚C) 5 I K A 2 J In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the following conditions are satisfied. (However the temperature for J zone dashing control is changed from 2°C to –5°C.) • When or ‚ is established 5 minutes after activation. Tcn ≤ Tc (n – 1) – 5 ‚ Tcn < Tc (n – 1) – 1 and Tcn ≤ Ta < 5°C Tcn: Tc temperature when 5 minutes elapsed after activation Tc (n – 1): Tc temperature at start time – 66 –

No. Item Outline of specifications Remarks 9 High-temp. release control 1) The heating operation is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. • When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone. • In [N] zone, the commanded frequency is held. • When [L] zone is detected, the commanded frequency is returned to the original value by approx. 6Hz every 60 seconds. However this control is ignored in case of the follower unit of the twin. Setup at shipment Control temp. (°C) A B 56 (54) 52 (52) Tc (˚C) Tcj A B L M N NOTE: When the operation has started or when Tc or Tcj < 30°C at start of the operation or after operation start, temperature is controlled between values in parentheses of A and B. Same status as that when “thermostat-OFF” (status that the air conditioner enters in the room temp. monitor mode when the temperature reached the setup temperature on the remote controller) 10 Drain pump control 1) In cooling operation (including Dry operation), the drain pump is usually operated. 2) If the float switch works while drain pump drives, the compressor stops, the drain pump continues the operation, and a check code is output. 3) If the float switch works while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx. 4 minutes, a check code is output. Check code [P10] 11 After-heat elimination When heating operation stops, in some cases, the indoor fan operates with (L) for approx. 30 seconds. is displayed. – 67 –

No.<br />

Item<br />

Outline of specifications<br />

Remarks<br />

9<br />

High-temp.<br />

release control<br />

1) The heating operation is performed as follows based on the<br />

detected temperature of Tc sensor or Tcj sensor.<br />

• When [M] zone is detected, the commanded frequency is<br />

decreased from the real operation frequency. After then<br />

the commanded frequency changes every 30 seconds<br />

while operation is performed in [M] zone.<br />

• In [N] zone, the commanded frequency is held.<br />

• When [L] zone is detected, the commanded frequency is<br />

returned to the original value by approx. 6Hz every<br />

60 seconds.<br />

However this control is<br />

ignored in case of the<br />

follower unit of the twin.<br />

Setup at shipment<br />

Control temp. (°C)<br />

A B<br />

56 (54) 52 (52)<br />

Tc (˚C)<br />

Tcj A<br />

B<br />

L<br />

M<br />

N<br />

NOTE:<br />

When the operation has started or when Tc or Tcj < 30°C at<br />

start of the operation or after operation start, temperature is<br />

controlled between values in parentheses of A and B.<br />

Same status as that<br />

when “thermostat-OFF”<br />

(status that the air<br />

conditioner enters in the<br />

room temp. monitor<br />

mode when the<br />

temperature reached the<br />

setup temperature on<br />

the remote controller)<br />

10<br />

Drain pump<br />

control<br />

1) In cooling operation (including Dry operation), the drain<br />

pump is usually operated.<br />

2) If the float switch works while drain pump drives, the<br />

compressor stops, the drain pump continues the operation,<br />

and a check code is output.<br />

3) If the float switch works while drain pump stops, the<br />

compressor stops and the drain pump operates. If the float<br />

switch keeps operating for approx. 4 minutes, a check code<br />

is output.<br />

Check code [P10]<br />

11<br />

After-heat<br />

elimination<br />

When heating operation stops, in some cases, the indoor fan<br />

operates with (L) for approx. 30 seconds.<br />

is displayed.<br />

– 67 –