SUPER DIGITAL
SUPER DIGITAL
SUPER DIGITAL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
No.<br />
Item<br />
Outline of specifications<br />
Remarks<br />
6<br />
Air speed selection<br />
1) Operation with (HH), (H), (L) or [AUTO] mode is carried<br />
out by the command from the remote controller.<br />
HH > H+ > H > L+ ><br />
L > UL<br />
2) When the air speed mode [AUTO] is selected, the air<br />
speed varies by the difference between Ta and Ts.<br />
<br />
Ta (˚C)<br />
+3.0<br />
+2.5<br />
+2.0<br />
+1.5<br />
+1.0<br />
+0.5<br />
Tsc<br />
–0.5<br />
HH<br />
(HH)<br />
H+ (HH)<br />
H (HH)<br />
L+ (H+)<br />
L (H)<br />
L (H)<br />
L (L+)<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
• Controlling operation in case when thermo of remote<br />
controller works is same as a case when thermo of the<br />
body works.<br />
• If the air speed has been changed once, it is not changed<br />
for 3 minutes. However when the air volume is exchanged,<br />
the air speed changes.<br />
• When cooling operation has started, select a downward<br />
slope for the air speed, that is, the high position.<br />
• If the temperature is just on the difference boundary, the<br />
air speed does not change.<br />
• Mode in the parentheses indicates one in automatic<br />
cooling operation.<br />
<br />
Ta (˚C)<br />
(–0.5) –1.0<br />
(0) Tsh<br />
(+0.5) +1.0<br />
(+1.0) +2.0<br />
(+1.5) +3.0<br />
(+2.0) +4.0<br />
L (L+)<br />
L+ (H)<br />
H (H+)<br />
H+<br />
(HH)<br />
HH<br />
(HH)<br />
E<br />
D<br />
C<br />
B<br />
A<br />
Value in the parentheses indicates one when thermostat of<br />
the remote controller works.<br />
Value without parentheses indicates one when thermostat of<br />
the body works.<br />
• If the air speed has been changed once, it is not changed<br />
for 1 minute. However when the air speed I exchanged, the<br />
air speed changes.<br />
• When heating operation has started, select an upward<br />
slope for the air speed, that is, the high position.<br />
• If the temperature is just on the difference boundary, the<br />
air speed does not change.<br />
• Mode in the parentheses indicates one in automatic<br />
heating operation.<br />
• In Tc ≥ 60°C, the air speed increases by 1 step.<br />
Tc: Indoor heat<br />
exchanger sensor<br />
temperature<br />
– 63 –