No.<br />

Item<br />

Outline of specifications<br />

Remarks<br />

3<br />

Room temp.<br />

control<br />

(Continued)<br />

2) Using the Item code 06, the setup temperature in heating<br />

operation can be corrected.<br />

Setup data<br />

0 2 4 6<br />

Shift of suction<br />

temperature in heating<br />

operation<br />

Setup temp. correction<br />

+0°C +2°C +4°C +6°C<br />

Setting at shipment<br />

Setup data 2<br />

4<br />

Automatic<br />

capacity control<br />

(GA control)<br />

1) Based on the difference between Ta and Ts, the operation<br />

frequency is instructed to the outdoor unit.<br />

2) Cooling operation<br />

Every 90 seconds, the room temperature difference<br />

between temperature detected by Ta and Ts and the<br />

varied room temperature value are calculated to obtain<br />

the correction value of the frequency command and then<br />

the present frequency command is corrected.<br />

Ta (n) – Ts (n) : Room temp. difference<br />

n<br />

: Counts of detection<br />

Ta (n-1) – Ts (n) : Varied room temp. value<br />

n – 1<br />

: Counts of detection of 90 seconds before<br />

3) Heating operation<br />

Every 1 minute (60 sec.), the room temperature difference<br />

between temperature detected by Ta and Ts and the<br />

varied room temperature value are calculated to obtain<br />

the correction value of the frequency command and then<br />

the present frequency command is corrected.<br />

Ts (n) – Ta (n) : Room temp. difference<br />

n<br />

: Counts of detection<br />

Ta (n) – Ta (n – 1): Varied room temp. value<br />

n – 1<br />

: Counts of detection of 1 minute before<br />

4) Dry operation<br />

The frequency correction control is same as those of the<br />

cooling operation.<br />

However the maximum frequency is limited to approximately<br />

“S6”.<br />

Note) When LOW is set up, the maximum frequency is<br />

limited to approximately “SB”.<br />

5<br />

Automatic<br />

cooling/heating<br />

control<br />

1) The judgment of selecting COOL/HEAT is carried out as<br />

shown below. When +1.5 exceeds against Tsh 10 minutes<br />

and after thermo.-OFF, heating operation (Thermo. OFF)<br />

exchanges to cooling operation. Description in the<br />

parentheses shows an example of cooling ON/OFF.<br />

Ta<br />

(˚C)<br />

+1.5<br />

Cooling<br />

Tsc: Setup temp. in<br />

cooling operation<br />

Tsh: Setup temp. in<br />

heating operation<br />

+ temp. correction of<br />

room temp. control<br />

or<br />

Tsc<br />

Tsh<br />

-1.5<br />

(Cooling OFF)<br />

Heating<br />

(Cooling ON)<br />

When –1.5 lowers against Tsc 10 minutes and after<br />

thermo. OFF, cooling operation (Thermo. OFF) exchanges<br />

to heating operation.<br />

2) For the automatic capacity control after judgment of<br />

cooling/heating, see Item 4.<br />

3) For temperature correction of room temp. control in<br />

automatic heating, see Item 3.<br />

– 62 –