8-2. Control Specifications<br />
No.<br />
Item<br />
Outline of specifications<br />
Remarks<br />
1<br />
When power<br />
supply is reset<br />
1) Distinction of outdoor unit<br />
When the power supply is reset, the outdoors are distinguished<br />
and the control is selected according to the<br />
distinguished result.<br />
2) Setting of indoor fan speed and existence of air direction<br />
adjustment<br />
Based on EEPROM data, select setting of the indoor fan<br />
speed and the existence of air direction adjustment.<br />
Air speed (rpm)/<br />
Air direction adjustment<br />
2<br />
Operation<br />
mode selection<br />
1) Based on the operation mode selecting command from the<br />
remote controller, the operation mode is selected.<br />
Remote controller<br />
command<br />
STOP<br />
FAN<br />
COOL<br />
DRY<br />
HEAT<br />
AUTO<br />
Control outline<br />
Air conditioner stops.<br />
Fan operation<br />
Cooling operation<br />
Dry operation<br />
Heating operation<br />
• COOL/HEAT operation mode is<br />
automatically selected by Ta, Ts<br />
and To for operation.<br />
• The operation is performed as<br />
shown in the following figure<br />
according to Ta value at the first<br />
time only. (In the range of Ts +<br />
α –1 < Ta < Ts + α + 1, Cooling<br />
thermo. OFF (Fan)/Setup air<br />
volume operation continues.)<br />
Ta: Room temp.<br />
Ts: Setup temp.<br />
To: Outside temp.<br />
Ta<br />
(˚C)<br />
+1.0<br />
Ts + α<br />
-1.0<br />
Cooling<br />
operation<br />
Cooling thermo. OFF (Fan)<br />
• Setup air volume<br />
Heating<br />
operation<br />
• α is corrected according to the outside temperature.<br />
Outside temp.<br />
No To<br />
To ≥ 24°C<br />
24 > To ≥ 18°C<br />
To < 18°C<br />
To error<br />
Correction value (α)<br />
0K<br />
–1K<br />
0K<br />
+1K<br />
0K<br />
k = deg<br />
3<br />
Room temp.<br />
control<br />
1) Adjustment range: Remote controller setup temperature (°C)<br />
COOL/DRY HEAT AUTO<br />
Wired type<br />
18 to 29<br />
18 to 29<br />
18 to 29<br />
Wireless type<br />
18 to 30<br />
16 to 30<br />
17 to 27<br />