8-2. Control Specifications<br />

No.<br />

Item<br />

Outline of specifications<br />

Remarks<br />

1<br />

When power<br />

supply is reset<br />

1) Distinction of outdoor unit<br />

When the power supply is reset, the outdoors are distinguished<br />

and the control is selected according to the<br />

distinguished result.<br />

2) Setting of indoor fan speed and existence of air direction<br />

adjustment<br />

Based on EEPROM data, select setting of the indoor fan<br />

speed and the existence of air direction adjustment.<br />

Air speed (rpm)/<br />

Air direction adjustment<br />

2<br />

Operation<br />

mode selection<br />

1) Based on the operation mode selecting command from the<br />

remote controller, the operation mode is selected.<br />

Remote controller<br />

command<br />

STOP<br />

FAN<br />

COOL<br />

DRY<br />

HEAT<br />

AUTO<br />

Control outline<br />

Air conditioner stops.<br />

Fan operation<br />

Cooling operation<br />

Dry operation<br />

Heating operation<br />

• COOL/HEAT operation mode is<br />

automatically selected by Ta, Ts<br />

and To for operation.<br />

• The operation is performed as<br />

shown in the following figure<br />

according to Ta value at the first<br />

time only. (In the range of Ts +<br />

α –1 < Ta < Ts + α + 1, Cooling<br />

thermo. OFF (Fan)/Setup air<br />

volume operation continues.)<br />

Ta: Room temp.<br />

Ts: Setup temp.<br />

To: Outside temp.<br />

Ta<br />

(˚C)<br />

+1.0<br />

Ts + α<br />

-1.0<br />

Cooling<br />

operation<br />

Cooling thermo. OFF (Fan)<br />

• Setup air volume<br />

Heating<br />

operation<br />

• α is corrected according to the outside temperature.<br />

Outside temp.<br />

No To<br />

To ≥ 24°C<br />

24 > To ≥ 18°C<br />

To < 18°C<br />

To error<br />

Correction value (α)<br />

0K<br />

–1K<br />

0K<br />

+1K<br />

0K<br />

k = deg<br />

3<br />

Room temp.<br />

control<br />

1) Adjustment range: Remote controller setup temperature (°C)<br />

COOL/DRY HEAT AUTO<br />

Wired type<br />

18 to 29<br />

18 to 29<br />

18 to 29<br />

Wireless type<br />

18 to 30<br />

16 to 30<br />

17 to 27<br />

– 61 –