8-1-3. Connection of Both Main (Sub) Remote Controller and Wireless Remote Controller Kit<br />
Indoor unit<br />
#1 (Master)<br />
Wireless remote controller kit<br />
Main (sub) master remote controller<br />
(Max. 2 units)<br />
Weekly timer<br />
Display LED<br />
Receiver P.C. board<br />
(MCC-1504)<br />
Display<br />
LCD<br />
Function<br />
setup<br />
Display<br />
LCD<br />
LCD<br />
driver<br />
Receive<br />
circuit<br />
Buzzer<br />
DC5V<br />
Power<br />
circuit<br />
MCU<br />
Remote controller<br />
communication circuit<br />
Function setup SW<br />
Grille up/down SW<br />
Temporary<br />
operation SW<br />
Display<br />
LED<br />
MCU<br />
Remote controller<br />
communication circuit<br />
Key<br />
switch<br />
DC5V<br />
Power<br />
circuit<br />
CN2<br />
CN1<br />
∗3<br />
DC5V<br />
Power<br />
circuit<br />
MCU<br />
Function<br />
setup<br />
Key<br />
switch<br />
Secondary<br />
battery<br />
A<br />
B<br />
A<br />
B<br />
A<br />
B<br />
#2<br />
(Follower)<br />
A<br />
B<br />
#3<br />
(Follower)<br />
A<br />
B<br />
Indoor control P.C. board (MCC-1570)<br />
DC20V<br />
DC5V<br />
DC12V<br />
Remote controller<br />
communication circuit<br />
EEPROM<br />
TA sensor<br />
× 4<br />
Louver<br />
motor<br />
Humidifier output<br />
Driver<br />
MCU<br />
TC sensor<br />
TCJ sensor<br />
Float input<br />
Same as left<br />
∗2<br />
Same as left<br />
∗2<br />
Drain<br />
pump<br />
HA<br />
Indoor<br />
fan motor<br />
DC280V<br />
Power circuit<br />
MCU<br />
Fan motor<br />
control circuit<br />
Outside<br />
output<br />
Run<br />
Warning<br />
Defrost<br />
Thermo. ON<br />
COOL<br />
HEAT<br />
FAN<br />
AC<br />
synchronous<br />
signal input circuit<br />
Auto grille<br />
panel<br />
Serial send/<br />
receive circuit<br />
1<br />
2<br />
3<br />
1<br />
2<br />
3<br />
1<br />
2<br />
3<br />
Outdoor unit<br />
Outdoor unit<br />
* Case of TCC-LINK adapter<br />
Case of TCC-LINK adapter<br />
(Option)<br />
TCC-LINK<br />
Central controller<br />
(Option)<br />
U3<br />
U4<br />
TCC-LINK<br />
adapter P.C. board<br />
(MCC-1440)<br />
TCC-LINK<br />
communication circuit<br />
1 2 3<br />
Outdoor unit<br />
Up to 8 units are connectable. ∗1<br />
∗1 However Max.7 units are connectable in case of<br />
mounting network adapter.<br />
∗2 The network adapter is mounted to only 1 unit.<br />
TCC-LINK adapter is mounted to the master unit.<br />
∗3 Connection of the weekly timer to the sub remote<br />
controller is unavailable.<br />
∗4 In the left system, set the wireless remote<br />
controller side as the follower remote controller<br />
when using the main (sub) wired remote controller<br />
as the master remote controller.<br />
– 60 –