14-2. Outdoor Unit<br />

RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E<br />

RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E<br />

No.<br />

Part name<br />

Procedure<br />

Remarks<br />

1<br />

Common<br />

procedure<br />

XCAUTIONX<br />

Front panel<br />

Never forget to put on the gloves at working<br />

time; otherwise an injury will be caused by<br />

the parts, etc.<br />

1. Detachment<br />

1) Stop operation of the air conditioner and<br />

then turn off switch of the breaker.<br />

2) Remove the front panel.<br />

(Hexagonal screw Ø4 × 10, 2 pcs.)<br />

• Remove the screws and then remove the<br />

front panel by pulling it downward.<br />

3) Remove the power supply cable and the<br />

indoor/outdoor connecting wire from the<br />

cord clamp and the terminal.<br />

4) Remove the top plate.<br />

(Hexagonal screw Ø4 × 10, 5 pcs.)<br />

2. Attachment<br />

1) Attach the top plate.<br />

(Hexagonal screw Ø4 × 10, 5 pcs.)<br />

2) Connect the power supply cable and the<br />

indoor/outdoor connecting wire to the<br />

terminal and then fix them with the cord<br />

clamp.<br />

Top plate<br />

XREQUIREMENTX<br />

For the power supply cable and the indoor/<br />

outdoor connecting wire, be sure fix them<br />

using the bundling band on the market along<br />

the crossover pipe so that they do not come to<br />

contact with the compressor, valve at gas side,<br />

pipe at gas side and discharge pipe.<br />

3) Attach the front panel.<br />

(Hexagonal screw Ø4 × 10, 2 pcs.)<br />

– 196 –