Revised 2: Jun., 2008<br />
13-4. Address Setup (Manual setting from remote controller)<br />
In case that addresses of the indoor units will be<br />
determined prior to piping work after cabling work<br />
• Set an indoor unit per a remote controller.<br />
• Turn on power supply.<br />
(Example of 2-lines cabling)<br />
(Real line: Cabling, Broken line: Refrigerant pipe)<br />
Outdoor<br />
1 2 3<br />
Outdoor<br />
1 2 3<br />
1 2 3<br />
Indoor<br />
A B<br />
1 2 3<br />
Indoor<br />
A B<br />
1 2 3<br />
Indoor<br />
A B<br />
1 2 3<br />
Indoor<br />
A B<br />
Line address → 1<br />
Indoor unit address → 1<br />
Group address → 1<br />
1<br />
2<br />
2<br />
2<br />
1<br />
2<br />
2<br />
2<br />
2<br />
1 Push SET + CL + TEST buttons simultaneously<br />
for 4 seconds or more.<br />
2 (← Line address)<br />
Using the temperature setup / buttons,<br />
set 12 to the item code.<br />
3 Using timer time / buttons, set the line address.<br />
4 Push SET button. (OK when display goes on.)<br />
5 (← Indoor unit address)<br />
A B<br />
Remote controller<br />
For the above example, perform setting by<br />
connecting singly the wired remote controller<br />
without remote controller inter-unit cable.<br />
Group address<br />
Individual : 0000<br />
Master unit : 0001<br />
In case of group control<br />
Sub unit : 0002<br />
Using the temperature setup / buttons, set 13 to the item code.<br />
6 Using timer time / buttons, set 1 to the line address.<br />
7 Push SET button. (OK when display goes on.)<br />
8 (← Group address)<br />
Using the temperature setup / buttons, set 14 to the item code.<br />
9 Using timer time / buttons, set 0000 to Individual, 0001 to Master unit, and 0002 to sub unit.<br />
10 Push SET button. (OK when display goes on.)<br />
11 Push TEST button.<br />
Setup completes. (The status returns to the usual stop status.)<br />
2, 5, 8<br />
END 11<br />
TEMP.<br />
FILTER<br />
RESET TEST<br />
TIMER SET<br />
TIME<br />
SET CL<br />
FAN<br />
SAVE<br />
SWING/FIX<br />
ON / OFF<br />
MODE<br />
VENT<br />
UNIT LOUVER<br />
3, 6, 9<br />
4, 7, 10<br />
1<br />
<br />
1 2 3 4 5 6 7 8 9 10 11 END<br />
– 178 –