13-2-2. Automatic Address Example from Unset Address (No miswiring)<br />

1. Standard (One outdoor unit)<br />

1) Single<br />

Revised 2: Jun., 2008<br />

1-1<br />

Individual<br />

(Master/Sub)<br />

2) Group operation (Twin, Triple operation)<br />

(Multiple outdoor units = Miltiple indoor units only with serial communication)<br />

2-1<br />

Sub/Header<br />

1-1<br />

Sub/Header<br />

1-2<br />

Sub/Follower<br />

3-1<br />

Master/Header<br />

3-2<br />

Sub/Follower<br />

3-3<br />

Sub/Follower<br />

Only turning on source power supply (Automatic completion)<br />

• Header unit: The header unit receives the indoor unit data (thermo status) of the follower (Without identical line<br />

address & indoor/outdoor serial) and then finally controls the outdoor compressor matching with<br />

its own thermo status.<br />

The header unit sends this command information to the follower unit.<br />

• Follower unit: The follower unit receives the indoor unit data from the header (With identical line address &<br />

indoor/outdoor serial) and then performs the thermo operation synchronized with the header unit.<br />

The follower unit sends own thermo ON/OFF demand to the header unit.<br />

(Example)<br />

No. 1-1 header unit sends/receives signal to/from No. 1-2 and No. 1-3 follower units.<br />

(It is not influenced by the line 2 or 3 address indoor unit.)<br />