13. ADDRESS SETUP<br />

Revised 2: Jun., 2008<br />

13-1. Address Setup Procedure<br />

When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor<br />

unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address<br />

setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while<br />

automatic address works. (Approx. 4 to 5 minutes)<br />

Setup of line address of outdoor unit,<br />

indoor unit address, and group address<br />

Completion of cabling work<br />

Do you arbitrarily set the<br />

indoor unit address?<br />

NO<br />

YES<br />

(MANUAL)<br />

NO<br />

Is refrigerant line 1 line?<br />

Is group control performed?<br />

NO<br />

YES<br />

YES<br />

(To AUTO address mode)<br />

Do you change setting after<br />

automatic setting at the first time?<br />

Connect one remote controller with<br />

one indoor unit (1 : 1) tentatively with<br />

communication cable.<br />

YES<br />

Turn on power of outdoor unit.<br />

Turn on power of outdoor unit.<br />

Turn on power of outdoor unit.<br />

Set to all indoor units one by one.<br />

( )<br />

After setup, completion change is of to address<br />

address/group manually.<br />

arbitral<br />

( )<br />

Setup address of finishes automatic<br />

4 to 5 minutes.<br />

within<br />

END<br />

• When the following addresses are not stored in the neutral memory (IC503) on the indoor P.C. board, a test<br />

run operation cannot be performed. (Unfixed data at shipment from factory)<br />

Item code<br />

Data at shipment<br />

Setup data range<br />

Line address<br />

12<br />

0099<br />

0001 (No. 1 unit) to 0064 (No. 64 unit)<br />

Indoor unit address<br />

13<br />

0099<br />

0001 (No. 1 unit) to 0064 (No. 64 unit)<br />

Max. value of indoor units in the identical refrigerant line<br />

Group address<br />

14<br />

0099<br />

0000 : Individual (Indoor units which are not controlled in a group)<br />

0001 : Master unit (1 indoor unit in group control)<br />

0002 : Sub unit (Indoor units other than master unit in group control)<br />

– 173 –