27.03.2014 Views

SUPER DIGITAL

SUPER DIGITAL

SUPER DIGITAL

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SW804<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

Operation when pushdown button switch SW801 is pushed<br />

4-way valve relay operation (For RY700, CN70 check)<br />

Turn on 4-way valve power relay (RY700).<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

[NOTE]<br />

In case of model adopting the self hold valve<br />

(RAV-SP1104AFE, RAV-SP1404T-E), the coil develops fever.<br />

Therefore do not perform this operation as coil is connected.<br />

Self-hold valve suction operation (Exchange to heating cycle)<br />

(For RY700 RY701, RY705, CN701 check)<br />

Turn on relay RY700, RY701, RY705.<br />

(CN701 between and „ : Voltage=Approx. +198 to 380V)<br />

This function works for 10 seconds and then is OFF.<br />

Self-hold valve separation operation (Exchange to cooling cycle)<br />

Turn on relay RY700.<br />

(CN701 between 1) and 4): Voltage=Approx. –198 to 380V)<br />

This function works for 10 seconds and then is OFF.<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SV valve relay operation (For RY702, CN702 check)<br />

Turn on SV valve relay (RY702).<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

* For RAV-SP1104 to RAV-SP1404, the part is not mounted, so<br />

do not operate.<br />

Heater output relay operation (For check RY703, CN703 check)<br />

Turn on relay for option heater (RY703).<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

Outside output relay operation (RY704, CN704)<br />

Turn on relay for outside output (RY704).<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

SW804<br />

ON<br />

1<br />

2 3 4<br />

SW804<br />

ON<br />

2 3 4<br />

1<br />

[CAUTION]<br />

Although these operations can be<br />

performed even during operation,<br />

basically perform operation while<br />

the unit stops.<br />

If performing this operation during<br />

driving the unit, it is dangerous<br />

because the pressure may change<br />

suddenly.<br />

(No operation especially)<br />

Relay operation change for outside output<br />

[CAUTION]<br />

Do not use this setting.<br />

– 172 –

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!