SUPER DIGITAL
SUPER DIGITAL
SUPER DIGITAL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SW804<br />
SW804<br />
ON<br />
1 2 3 4<br />
SW804<br />
ON<br />
1 2 3 4<br />
SW804<br />
ON<br />
1 2 3 4<br />
Operation when pushdown button switch SW801 is pushed<br />
4-way valve relay operation (For RY700, CN70 check)<br />
Turn on 4-way valve power relay (RY700).<br />
When pushing SW801 again or when 2 minutes elapsed, the<br />
operation returns to the normal control.<br />
[NOTE]<br />
In case of model adopting the self hold valve<br />
(RAV-SP1104AFE, RAV-SP1404T-E), the coil develops fever.<br />
Therefore do not perform this operation as coil is connected.<br />
Self-hold valve suction operation (Exchange to heating cycle)<br />
(For RY700 RY701, RY705, CN701 check)<br />
Turn on relay RY700, RY701, RY705.<br />
(CN701 between and „ : Voltage=Approx. +198 to 380V)<br />
This function works for 10 seconds and then is OFF.<br />
Self-hold valve separation operation (Exchange to cooling cycle)<br />
Turn on relay RY700.<br />
(CN701 between 1) and 4): Voltage=Approx. –198 to 380V)<br />
This function works for 10 seconds and then is OFF.<br />
SW804<br />
ON<br />
1 2 3 4<br />
SW804<br />
ON<br />
1 2 3 4<br />
SW804<br />
ON<br />
1 2 3 4<br />
SV valve relay operation (For RY702, CN702 check)<br />
Turn on SV valve relay (RY702).<br />
When pushing SW801 again or when 2 minutes elapsed, the<br />
operation returns to the normal control.<br />
* For RAV-SP1104 to RAV-SP1404, the part is not mounted, so<br />
do not operate.<br />
Heater output relay operation (For check RY703, CN703 check)<br />
Turn on relay for option heater (RY703).<br />
When pushing SW801 again or when 2 minutes elapsed, the<br />
operation returns to the normal control.<br />
Outside output relay operation (RY704, CN704)<br />
Turn on relay for outside output (RY704).<br />
When pushing SW801 again or when 2 minutes elapsed, the<br />
operation returns to the normal control.<br />
SW804<br />
ON<br />
1<br />
2 3 4<br />
SW804<br />
ON<br />
2 3 4<br />
1<br />
[CAUTION]<br />
Although these operations can be<br />
performed even during operation,<br />
basically perform operation while<br />
the unit stops.<br />
If performing this operation during<br />
driving the unit, it is dangerous<br />
because the pressure may change<br />
suddenly.<br />
(No operation especially)<br />
Relay operation change for outside output<br />
[CAUTION]<br />
Do not use this setting.<br />
– 172 –