4) Specific operation for maintenance check (SW801, SW804)<br />

The following specific operations for the maintenance check are performed by operation of SW801 or<br />

SW804.<br />

a) Select DIP switch SW804. (See table below)<br />

b) Push the pushdown button switch SW801 for approx. 1 second.<br />

c) The following functions start. While each function starts, LED D805 (Green) flashes.<br />

d) When pushing the pushdown button switch SW801 again for approx. 1 second, when selecting DIP<br />

switch SW804 or when the specified time of each function elapsed, each function stops and<br />

LED D805 (Green) returns to the continuous lighting.<br />

<br />

<br />

SW804<br />

SW804<br />

2 3 4<br />

Operation when pushdown button switch SW801 is pushed<br />

Refrigerant recovery operation<br />

The outdoor unit performs cooling operation. The indoor unit does not work by this operation<br />

alone. Therefore operate the fan beforehand. (Refer → 12-4-1. Refrigerant Recovery Control)<br />

ON<br />

1<br />

SW804<br />

2 3 4<br />

Indoor cooling test run demand<br />

The cooling test run is performed. (→ Note 1)<br />

ON<br />

1<br />

SW804<br />

2 3 4<br />

Indoor heating test run demand<br />

The heating test run is performed. (→ Note 1)<br />

ON<br />

1<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

SW804<br />

ON<br />

1 2 3 4<br />

Fan motor forced operation<br />

Drive the fan motor forcedly.<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

(No operation especially)<br />

PMV full open operation<br />

Open PMV (Pulse Motor Valve) fully.<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

PMV full close operation<br />

Close PMV (Pulse Motor Valve) fully.<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

PMV middle opening operation<br />

Set PMV (Pulse Motor Valve) to middle opening<br />

(250 pulses).<br />

When pushing SW801 again or when 2 minutes elapsed, the<br />

operation returns to the normal control.<br />

[NOTE]<br />

Although these operations can<br />

be performed even during<br />

operation, basically perform<br />

operation while the unit stops.<br />

If performing this operation<br />

during driving the unit, it is<br />

dangerous because the<br />

pressure may change suddenly.<br />

Note 1)<br />

Note 2)<br />

Indoor cooling test run demand / Indoor heating test run demand<br />

Only when combining with the following indoor unit, cooling/heating operation can be performed from the<br />

outdoor unit.<br />

Test run is available: Indoor unit of 4 series and after (RAV-SM∗∗∗4UT-E etc.)<br />

Test run is unavailable: Indoor units other than the above-mentioned indoor units, or indoor units other<br />

than above-mentioned indoor units are included in the twin connection.<br />

The forced test run by this setting cannot be cleared on the indoor remote controller.<br />

Be sure to clear the test run by operation of the outdoor unit. (Push SW801 again for 1 second.)<br />