SUPER DIGITAL
SUPER DIGITAL
SUPER DIGITAL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3) Sensor, current, compressor operation frequency, PMV opening display<br />
<br />
The values detected by the controller, such as temperature sensor or current value are simply confirmed.<br />
(Legend)<br />
l D800 (Yellow)<br />
l D801 (Yellow)<br />
l D802 (Yellow)<br />
l D803 (Yellow)<br />
l D804 (Yellow)<br />
¡ D805 (Green)<br />
l : Go off, ¡ : Go on<br />
Item<br />
setup<br />
TD<br />
SW803<br />
ON<br />
2 3 4<br />
1<br />
Temperature sensor (°C)<br />
TE<br />
SW803<br />
ON<br />
2 3 4<br />
1<br />
TS<br />
SW803<br />
ON<br />
2 3 4<br />
1<br />
TO<br />
SW803<br />
ON<br />
2 3 4<br />
1<br />
TL<br />
SW803<br />
ON<br />
2 3 4<br />
1<br />
Current<br />
(A)<br />
Compressor<br />
operation<br />
frequency<br />
(rpm)<br />
PMV<br />
opening<br />
(Pulse)<br />
SW803 SW803 SW803<br />
TH<br />
SW803<br />
TA<br />
SW803<br />
TC<br />
SW803<br />
TCJ<br />
SW803<br />
2 3 4<br />
2 3 4<br />
2 3 4<br />
LED<br />
display<br />
ON<br />
2 3 4<br />
1<br />
ON<br />
2 3 4<br />
1<br />
ON<br />
2 3 4<br />
1<br />
ON<br />
2 3 4<br />
1<br />
ON<br />
1<br />
ON<br />
1<br />
ON<br />
1<br />
lllll¡<br />
¡llll¡<br />
l¡lll¡<br />
¡¡lll¡<br />
ll¡ll¡<br />
¡l¡ll¡<br />
l¡¡ll¡<br />
¡¡¡ll¡<br />
lll¡l¡<br />
¡ll¡l¡<br />
l¡l¡l¡<br />
¡¡l¡l¡<br />
ll¡¡l¡<br />
¡l¡¡l¡<br />
l¡¡¡l¡<br />
¡¡¡¡l¡<br />
llll¡¡<br />
¡lll¡¡<br />
l¡ll¡¡<br />
¡¡ll¡¡<br />
ll¡l¡¡<br />
¡l¡l¡¡<br />
l¡¡l¡¡<br />
¡¡¡l¡¡<br />
lll¡¡¡<br />
¡ll¡¡¡<br />
l¡l¡¡¡<br />
¡¡l¡¡¡<br />
ll¡¡¡¡<br />
¡l¡¡¡¡<br />
l¡¡¡¡¡<br />
¡¡¡¡¡¡<br />
Below –25<br />
–25 to –21<br />
–20 to –16<br />
–15 to –11<br />
–10 to – 5<br />
–5 to –1<br />
0 to 4<br />
5 to 9<br />
10 to 14<br />
15 to 19<br />
20 to 24<br />
25 to 29<br />
30 to 34<br />
35 to 39<br />
40 to 44<br />
45 to 49<br />
50 to 54<br />
55 to 59<br />
60 to 64<br />
65 to 69<br />
70 to 74<br />
75 to 79<br />
80 to 84<br />
85 to 89<br />
90 to 94<br />
95 to 99<br />
100 to 104<br />
105 to 109<br />
110 to 114<br />
115 to 119<br />
Over 120<br />
Sensor error, unconnected<br />
0 to 0.9<br />
1 to 1.9<br />
2 to 2.9<br />
3 to 3.9<br />
4 to 4.9<br />
5 to 5.9<br />
6 to 6.9<br />
7 to 7.9<br />
8 to 8.9<br />
9 to 9.9<br />
10 to 10.9<br />
11 to 11.9<br />
12 to 12.9<br />
13 to 13.9<br />
14 to 14.9<br />
15 to 15.9<br />
16 to 16.9<br />
17 to 17.9<br />
18 to 18.9<br />
19 to 19.9<br />
20 to 20.9<br />
21 to 21.9<br />
22 to 22.9<br />
23 to 23.9<br />
24 to 24.9<br />
25 to 25.9<br />
26 to 26.9<br />
27 to 27.9<br />
28 to 28.9<br />
29 to 29.9<br />
30 to 30.9<br />
Over 31<br />
0 to 4<br />
5 to 9<br />
10 to 14<br />
15 to 19<br />
20 to 24<br />
25 to 29<br />
30 to 34<br />
35 to 39<br />
40 to 44<br />
45 to 49<br />
50 to 54<br />
55 to 59<br />
60 to 64<br />
65 to 69<br />
70 to 74<br />
75 to 79<br />
80 to 84<br />
85 to 89<br />
80 to 84<br />
95 to 99<br />
100 to 104<br />
105 to 109<br />
110 to 114<br />
115 to 119<br />
120 to 124<br />
125 to 129<br />
130 to 134<br />
135 to 139<br />
140 to 144<br />
145 to 149<br />
150 to 154<br />
Over 155<br />
∗ As TD, TL and TH are sensors for high temperature, there is error at normal temperature or below position.<br />
∗ For current value, the current for the outdoor unit only is displayed.<br />
0 to 19<br />
20 to 39<br />
40 to 59<br />
60 to 79<br />
80 to 99<br />
100 to 119<br />
120 to 139<br />
140 to 159<br />
160 to 179<br />
180 to 199<br />
200 to 219<br />
220 to 239<br />
240 to 259<br />
260 to 279<br />
280 to 299<br />
300 to 319<br />
320 to 339<br />
340 to 359<br />
360 to 379<br />
380 to 399<br />
400 to 419<br />
420 to 439<br />
440 to 459<br />
460 to 479<br />
480 to 499<br />
500<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
– 170 –