Revised 2: Mar., 2008<br />

12-4. Outdoor Unit<br />

12-4-1. Refrigerant Recovery Control<br />

The “ozone destruction coefficient” of HFC refrigerant is 0 and the<br />

discharge regulation is set as anathermal effect gas.<br />

To this model, a switch which can perform the refrigerant recovery<br />

(pump down) by the outdoor unit is mounted so that it is easy to<br />

react against the environment at reinstalling or rejection time.<br />

ON<br />

1 2 3 4<br />

W804: All OFF (As initial status)<br />

SW801: Push for 1 second.<br />

[Operation method]<br />

1) Set the mode of the indoor unit to fan mode.<br />

2) Set all DIP switch SW804 to OFF (Initial status) and then push<br />

the button switch SW801 for approx. 1 second. The cooling<br />

operation starts. (During this time, D805 (Green LED) flashes.)<br />

This operation finishes by 10 minutes.<br />

3) After operation for 3 minutes or more, close valve at liquid side.<br />

4) After recovery of refrigerant, close valve at gas side.<br />

5) Push the button switch SW801 again for approx. 1 second.<br />

The outdoor unit stops.<br />

D800<br />

D801<br />

D802<br />

D803<br />

D804<br />

D805<br />

The D805 (Green LED)<br />

flashes.<br />

ON<br />

ON<br />

1 2 3 4<br />

1 2 3 4<br />

6) Stop the indoor unit and then turn off the power supply.<br />

12-4-2. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.)<br />

The following settings are available by DIP switch setup and jumper line setup.<br />

Function<br />

Set position<br />

Control contents<br />

High static<br />

pressure setup<br />

Existing<br />

piping setup<br />

ON<br />

SW802<br />

1 2 3 4<br />

High static pressure setup<br />

Existing piping setup<br />

Power save setup<br />

Snow-proof fan control<br />

Turn the switch to ON when mounting a duct to the discharge port of the<br />

outdoor unit. Add 3 taps to the upper limit value of the outdoor fan tap.<br />

The operation is performed with<br />

(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).<br />

In this case, the upper limit value of static pressure for duct is 5Pa or less<br />

on 25°C degrees and please use straight duct.<br />

In this case, the outdoor noise level may increase.<br />

Turn the switch to ON when Ø19.1 is used for the existing pipe.<br />

In this case, the heating capacity may lower according to outside temp. and<br />

indoor temp. in heating operation.<br />

Power save<br />

setup<br />

Snow-proof<br />

fan control<br />

Defrost<br />

time change<br />

Max. frequency<br />

change<br />

∗ all are OFF at shipment.<br />

J805, J806<br />

J807<br />

Turn the switch to ON when using the power save function.<br />

The control to lower the compressor frequency (Approx. –10%) is<br />

performed by indoor heat exchanger temp. in heating operation.<br />

When snow enters from clearance of the fan guard or heat exchanger into<br />

blast path and it is accumulated, the control to prevent generation of motor<br />

lock is validated.<br />

When outside temp. is below 0°C though the compressor stops, the<br />

outdoor fan operates with W5.<br />

The defrost interval is cut to shorten it than the standard status.<br />

For contents of control and cutting method, refer to Section<br />

9-2-10. Defrost control.<br />

When it is needed to lower the maximum value of the compressor<br />

frequency, cut the jumper line. Max. frequency at cooling/heating is lowered.<br />

In this case the Max. capacity decreases.<br />

Max. frequency of compressor<br />

Model<br />

RAV-SP1104<br />

RAV-SP1404<br />

COOL HEAT COOL HEAT<br />

Standard status<br />

When J807 is cut<br />

53.4 71.4 64.2 90.6<br />

53.4 64.2 64.2 72.0<br />

Cooling-only<br />

setup<br />

J808<br />

When using the air conditioner as a cooling-only conditioner, cut the jumper<br />

line. (An air conditioner can be changed to cooling-only conditioner by “0F”<br />

of DN code on the remote controller.)<br />

– 166 –