4. How to set louver lock (Louver fix)<br />
<br />
1<br />
UNIT LOUVER<br />
Push (At the right side of the button) for<br />
4 seconds or more during stop of the operation.<br />
• flashes.<br />
2 Push UNIT LOUVER (At the left side of the button) and<br />
select the unit to be set.<br />
• Every pushing the button, the unit No. changes.<br />
UNIT No.<br />
1–1<br />
The fan of the selected unit rotates and the<br />
louver swings.<br />
3 Push temp. set / to display the<br />
louver No. of which air direction is to be fixed.<br />
• The selected louver swings.<br />
4 Push TIMER SET / and select air<br />
direction of the louver of which swinging you<br />
do not want.<br />
Code<br />
0001 0002 0003<br />
0004<br />
UNIT No.<br />
1–2<br />
UNIT No.<br />
1–4<br />
0005<br />
UNIT No.<br />
1–3<br />
[F1] [F2] [F3] [F4]<br />
∗ If selecting above „ and …, there may be fear of<br />
dewing in cooling time.<br />
5 Push SET to determine the setup contents.<br />
• When the setup was determined, mark goes on.<br />
⎛<br />
⎞<br />
To set continuously the louver lock of the other unit,<br />
repeat operations from 2 but from 3 to set the other<br />
⎜<br />
⎟<br />
⎝louver lock in the same unit, respectively. ⎠<br />
6 Push TEST to finish the setup.<br />
Refrigerant pipe<br />
Electric parts box<br />
Drain pipe<br />
NOTIFICATION<br />
03<br />
04 02<br />
01<br />
• Even if louver lock works, the louver temporarily<br />
moves in the following cases.<br />
1) During stop<br />
2) At start of heating operation<br />
3) During defrost operation<br />
4) During thermostat OFF<br />
5. How to clear louver lock<br />
<br />
In the item 4 of the louver lock setup<br />
procedure, set the air direction to 0000.<br />
• mark goes off.<br />
The operations from 1 to 3, 5<br />
and 6 are same as those of the Code 0000<br />
louver lock.<br />
6. How to set contents of save operation<br />
In combination with outdoor units before 4 series,<br />
the displayed setup value exchanges, but the real<br />
operation is “75% fixed”.<br />
SAVE<br />
1 Push for 4 seconds or more during<br />
stop of the operation.<br />
• flashes.<br />
2 Push UNIT LOUVER (At the left side of the button)<br />
and select the unit to be set.<br />
• Every pushing the button, the unit No. changes.<br />
The fan of the selected unit rotates and the<br />
louver swings.<br />
UNIT No.<br />
1–1<br />
UNIT No.<br />
1–2<br />
UNIT No.<br />
1–3<br />
UNIT No. 1–4<br />
3 Determine the capacity restricted value when<br />
pushing the save button of TIMER SET / .<br />
• Every pushing the button, the capacity restricted<br />
value can be set at 1% interval in the<br />
range between 100% and 50%.<br />
∗ The setting at shipment is 75%.<br />
0001 to 0005<br />
(Louver fixed position code)<br />
Louver<br />
No.<br />
∗ F1 displayed at the item code on the remote<br />
controller means that the 01 louver was selected<br />
as shown in the figure.<br />
Setup value at saving<br />
4 Push SET and then push TEST to finish the setup.<br />