6. External view of P.C. board assembly<br />
Terminator (SW01)<br />
52<br />
7. Address setup<br />
In addition to set up the central control address, it is necessary to change the indoor unit number.<br />
(Line/Indoor/Group address). For details, refer to TCC-LINK Adapter Installation Manual.<br />
85<br />
12-3. How to Set up Central Control Address Number<br />
When connecting the indoor unit to the central control remote controller using TCC-LINK adapter, it is necessary<br />
to set up the central control address number.<br />
• The central control address number is displayed as the line No. of the central control remote controller.<br />
1. Setup from remote controller at indoor unit side<br />
∗ If you use the network adapter P.C. board, it is effective only when No. 7 of setup switch SW01 on P.C.<br />
board is turned off.<br />
Perform setup while the unit stops.<br />
1 Push TEST + VENT buttons for 4 seconds or more.<br />
When group control is executed, first the unit No. is displayed and all the indoor units in the group<br />
control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)<br />
(Keep displayed status without pushing UNIT LOUVER button.)<br />
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address<br />
are displayed.<br />
2 Using temperature setup<br />
TEMP.<br />
buttons, specify item code 03.<br />
3 Using timer time<br />
TIME<br />
buttons, select the setup data.<br />
The setup data is shown in the table below (Table 1).<br />
4 Push SET button. (OK if display goes on.)<br />
• To change the item to be set up, return to Procedure 2.<br />
(Fig.1)<br />
5 Push TEST button.<br />
The status returns to usual stop status.<br />
Setup data<br />
0001<br />
0002<br />
0003<br />
:<br />
0064<br />
0099<br />
(Table 1)<br />
Central control address No.<br />
1<br />
2<br />
3<br />
:<br />
64<br />
Unset (Setup at shipment from factory)<br />
2<br />
1<br />
5<br />
FILTER<br />
RESET<br />
TEMP.<br />
TEST<br />
TIMER SET<br />
TIME<br />
SET CL<br />
FAN<br />
SAVE<br />
SWING/FIX<br />
ON / OFF<br />
MODE<br />
VENT<br />
UNIT LOUVER<br />
3<br />
1<br />
4<br />