4. Wiring specifications<br />

• Use 2-core with no polar wire.<br />

• Match the length of wire to wire length of the central<br />

control system.<br />

If mixed in the system, the wire length is lengthened<br />

with all indoor/outdoor inter-unit wire length at side.<br />

• To prevent noise trouble, use 2-core shield wire.<br />

No. of wires<br />

• Connect the shield wire by closed-end connection and apply open process (insulating process) to the last<br />

terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter<br />

unit setup)<br />

2<br />

CAUTION<br />

Size<br />

Up to 1000m: twisted wire 1.25mm 2<br />

Up to 2000m: twisted wire 2.0mm 2<br />

Central control device<br />

U1 U2<br />

1) Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)<br />

2) Apply open process to the last terminal (insulating process).<br />

3) Ground earth wire to 1 point at indoor unit side.<br />

Caution 2<br />

Caution 1<br />

Central control system wiring<br />

Caution 3<br />

Outdoor unit<br />

1 2 3<br />

1 2 3 1 2 3 1 2 3<br />

: TCC-LINK adapter<br />

(This option)<br />

Indoor unit<br />

Master<br />

unit<br />

Sub unit<br />

U3 U4 1 2 3 U3 U4 1 2 3<br />

1 2 3<br />

Sub unit<br />

1 2 3 U3 U4<br />

Master unit<br />

1 2 3<br />

A B<br />

A B<br />

A B<br />

A B<br />

A B<br />

Remote controller<br />

Remote controller Remote controller Remote controller<br />

(Group operation)<br />

Earth terminal<br />

(Twin operation)<br />

5. P.C. board switch (SW01) setup<br />

When performing collective control by customized setup only, the setup of terminator is necessary.<br />

• Using SW01, set up the terminator.<br />

• Set up the terminator to only the adapter connected to the indoor unit of least line address No.<br />

Central control device<br />

U1<br />

U3<br />

U2<br />

U4<br />

Central control device<br />

U1<br />

U3<br />

U2<br />

U4<br />

Central control devices: Max. 10 units<br />

Refrigerant line 1<br />

Refrigerant line 2<br />

Refrigerant line 3<br />

Refrigerant line 4<br />

Outdoor unit<br />

1 2 3<br />

1 2 3<br />

1 2 3<br />

1 2 3<br />

Indoor/outdoor inter-unit wire (AC230V serial)<br />

Central control system wiring<br />

Indoor unit<br />

Master<br />

unit<br />

Sub<br />

unit<br />

U3 U4 1 2 3 U3 U4 1 2 3<br />

1 2 3<br />

Sub unit<br />

1 2 3 U3 U4<br />

* Wiring for No.1 and 2 only<br />

Master unit<br />

1 2 3<br />

TCC-LINK adapter<br />

This product<br />

( sold separately )<br />

A B<br />

Remote controller<br />

A B<br />

A B<br />

A B<br />

A B<br />

Remote controller wiring<br />

Remote controller Remote controller Remote controller Remote controller<br />

Group operation (Max. 8 units)<br />

Twin operation<br />

Line address<br />

SW01 Bit 1<br />

SW01 Bit 2<br />

Remarks<br />

1<br />

ON<br />

OFF<br />

Turn SW01 Bit 1 to ON.<br />

(Reference) Setup contents of switch<br />

SW01<br />

Bit 1 Bit 1<br />

Terminator<br />

OFF<br />

ON<br />

OFF<br />

ON<br />

OFF<br />

OFF<br />

ON<br />

ON<br />

None<br />

100Ω<br />

75Ω<br />

43Ω<br />

2<br />

OFF<br />

OFF<br />

As status shipped from factory<br />

4<br />

OFF<br />

OFF<br />

As status shipped from factory<br />

Remarks<br />

Mixed with multi (Link wiring) at shipment from factory<br />

Central control by digital inverter only<br />

Spare<br />

Spare<br />

(OFF at shipment from factory)<br />

(OFF at shipment from factory)<br />

– 159 –