12-2. Setup at Local Site / Others<br />

Model name: TCB-PCNT30TLE2<br />

12-2-1. TCC-LINK Adapter (For TCC-LINK Central Control)<br />

1. Function<br />

This model is an optional P.C. board to connect the indoor unit to TCC-LINK (Central controller).<br />

2. Microprocessor block diagram<br />

Indoor unit<br />

CN050<br />

Indoor control<br />

P.C. board<br />

CN041<br />

Remote controller<br />

Terminal block<br />

(A, B)<br />

TCC-LINK adapter P.C. board<br />

CN51<br />

TCC-LINK<br />

communication circuit<br />

CN40<br />

Terminal<br />

resistance<br />

SW01<br />

MCC-1440<br />

Central controller<br />

TCC-LINK<br />

Communication units : Total 64 units<br />

Communication distance : 2000 m<br />

3. TCC-LINK wiring connection<br />

CAUTION<br />

1) When controlling customized setup collectively, TCC-LINK adapter (This option) is required.<br />

2) In case of group operation or twin operation, the adapter is necessary to be connected to the main unit.<br />

3) Connect the central control devices to the central control system wiring.<br />

4) When controlling collectively customized setup only, turn on only Bit 1 of SW01 of the least line of the system<br />

address No. (OFF when shipped from the factory)<br />

* In case of customized setup, the address is necessary to be set up again from the wired remote<br />

controller after automatic addressing.<br />

Central control device<br />

U1<br />

U3<br />

U2<br />

U4<br />

Central control device<br />

U1<br />

U3<br />

U2<br />

U4<br />

Central control devices: Max. 10 units<br />

Refrigerant line 1<br />

Refrigerant line 2<br />

Refrigerant line 3<br />

Refrigerant line 4<br />

Outdoor unit<br />

1 2 3<br />

1 2 3<br />

1 2 3<br />

1 2 3<br />

Caution 3<br />

Indoor/outdoor inter-unit wire (AC230V serial)<br />

Central control system wiring<br />

Indoor unit<br />

U3 U4<br />

1 2 3<br />

Master<br />

unit<br />

Sub<br />

unit<br />

U3 U4 1 2 3<br />

1 2 3<br />

Sub unit<br />

1 2 3 U3 U4<br />

* Wiring for No.1 and 2 only<br />

Master unit<br />

1 2 3<br />

TCC-LINK adapter<br />

This product<br />

sold separately<br />

( ) Caution 1<br />

A B<br />

Remote controller<br />

Caution 2<br />

A B<br />

Remote controller<br />

wiring<br />

A B<br />

A B<br />

Remote controller Remote controller Remote controller<br />

A B<br />

Group operation (Max. 8 units)<br />

Twin operation<br />

Indoor units in all refrigerant lines: Max. 64 units<br />

[If mixed with multi model (Link wiring), multi indoor units are included.]<br />

* However group sub units and twin sub units of customized setup are not included in number of the units.<br />

– 158 –