n Indoor unit power-ON sequence<br />

Power ON<br />

<br />

• The unit without power feed waits entirely<br />

→ Waiting status is released by system start<br />

• Reboot when power is fed on the way<br />

<br />

Gr construction check<br />

Not normal<br />

3 minutes elapse<br />

NO<br />

Normal<br />

∗ Gr normal<br />

1) There is no duplicated indoor unit address.<br />

2) There is no invalid indoor unit address.<br />

3) Individual unit and master/follower units<br />

are not intermingled.<br />

4) Only a unit for individual.<br />

5) A master indoor unit and 1 or more<br />

follower indoor units for Gr.<br />

YES<br />

System start<br />

Automatic address starts.<br />

(Approx. 1 minute up to finish)<br />

<br />

Outdoor model distinction (10 seconds) (Indoor unit)<br />

Twin Master/follower distinction (Indoor unit)<br />

Gr construction, louver information (Remote controller)<br />

<br />

• Power supply/Indoor/Outdoor serial and Gr wiring: OK<br />

• Powers of all indoor units are turned on within 3 minutes.<br />

• Reception time for remote controller operation<br />

(After power supply was turned on)<br />

1) When address is OK : Approx. 50 seconds<br />

2) In AUTO address : Approx. 4 to 5 minutes<br />

Remote controller operation is available.<br />

(Approx. 50 seconds after power-ON)<br />

<br />

Regular communication between indoor units (Every 30 seconds) (Master/Follower)<br />

Regular communication on the identical pipe (every 30 seconds) (Twin Master/Follower)<br />

(When the above status changes, immediately communicates.)<br />

(Repetition)<br />

• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot<br />

receive regular communication from the master unit and regular communication on identical pipe within<br />

120 seconds after power was turned on, it reboots (system reset).<br />

→ The operation starts from judgment of automatic address (Gr construction check) again.<br />

(If the address of the master unit was determined in the previous time, the power fed to the master unit and<br />

reboot works, the master unit may change though the indoor unit line address is not changed.)<br />

– 157 –