n Indoor unit power-ON sequence<br />
Power ON<br />
<br />
• The unit without power feed waits entirely<br />
→ Waiting status is released by system start<br />
• Reboot when power is fed on the way<br />
<br />
Gr construction check<br />
Not normal<br />
3 minutes elapse<br />
NO<br />
Normal<br />
∗ Gr normal<br />
1) There is no duplicated indoor unit address.<br />
2) There is no invalid indoor unit address.<br />
3) Individual unit and master/follower units<br />
are not intermingled.<br />
4) Only a unit for individual.<br />
5) A master indoor unit and 1 or more<br />
follower indoor units for Gr.<br />
YES<br />
System start<br />
Automatic address starts.<br />
(Approx. 1 minute up to finish)<br />
<br />
Outdoor model distinction (10 seconds) (Indoor unit)<br />
Twin Master/follower distinction (Indoor unit)<br />
Gr construction, louver information (Remote controller)<br />
<br />
• Power supply/Indoor/Outdoor serial and Gr wiring: OK<br />
• Powers of all indoor units are turned on within 3 minutes.<br />
• Reception time for remote controller operation<br />
(After power supply was turned on)<br />
1) When address is OK : Approx. 50 seconds<br />
2) In AUTO address : Approx. 4 to 5 minutes<br />
Remote controller operation is available.<br />
(Approx. 50 seconds after power-ON)<br />
<br />
Regular communication between indoor units (Every 30 seconds) (Master/Follower)<br />
Regular communication on the identical pipe (every 30 seconds) (Twin Master/Follower)<br />
(When the above status changes, immediately communicates.)<br />
(Repetition)<br />
• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot<br />
receive regular communication from the master unit and regular communication on identical pipe within<br />
120 seconds after power was turned on, it reboots (system reset).<br />
→ The operation starts from judgment of automatic address (Gr construction check) again.<br />
(If the address of the master unit was determined in the previous time, the power fed to the master unit and<br />
reboot works, the master unit may change though the indoor unit line address is not changed.)<br />
– 157 –