n Calling of error history<br />
<br />
The error contents in the past can be called.<br />
<br />
1 Push SET + TEST buttons simultaneously for<br />
4 seconds or more to call the service check mode.<br />
Service Check goes on, the item code 01 is displayed, and<br />
then the content of the latest alarm is displayed. The number<br />
and error contents of the indoor unit in which an error occurred<br />
are displayed.<br />
2 In order to monitor another error history, push the set<br />
temperature / buttons to change the error<br />
history No. (Item code).<br />
Item code 01 (Latest) → Item code 04 (Old)<br />
NOTE : 4 error histories are stored in memory.<br />
3 Pushing TEST button returns the display to usual display.<br />
REQUIREMENT<br />
Do not push CL<br />
button, otherwise all the error histories of the<br />
indoor unit are deleted.<br />
FILTER<br />
RESET<br />
TEMP.<br />
TEST<br />
2 3 1<br />
TIMER SET<br />
SET<br />
TIME<br />
<br />
1 2 3<br />
CL<br />
FAN<br />
SAVE<br />
SWING/FIX<br />
ON / OFF<br />
MODE<br />
VENT<br />
UNIT LOUVER<br />
Returned to usual display<br />
(Group control operation)<br />
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.<br />
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to<br />
setting on the remote controller.<br />
<br />
OUT<br />
IN<br />
1-1<br />
OUT<br />
IN Master<br />
2-1<br />
OUT<br />
IN 3-1<br />
OUT<br />
IN 4-1<br />
OUT<br />
IN 7-1<br />
Max. 8 units<br />
Remote controller<br />
1. Display range on remote controller<br />
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the<br />
master unit is reflected on the remote controller.<br />
2. Address setup<br />
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic<br />
address.<br />
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the<br />
system is rebooted and the automatic address setting will be judged again.<br />
1) Connect 3 In/Out cables surely.<br />
2) Check line address/indoor address/group address of the unit one by one.<br />
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the<br />
unit No. is not duplicated with one of another unit.<br />