12-1-6. Monitor Function of Remote Controller Switch<br />
n Calling of sensor temperature display<br />
<br />
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor<br />
mode from the remote controller.<br />
<br />
1 Push TEST + CL buttons simultaneously for 4 seconds to<br />
call the service monitor mode.<br />
The service monitor goes on, the master indoor unit No. is<br />
displayed at first and then the temperature of item code 00 is<br />
displayed.<br />
ò<br />
TEMP.<br />
2 Push temperature set buttons and then change<br />
the item code of data to be monitored.<br />
The item code list is shown below.<br />
TEMP.<br />
FILTER<br />
RESET TEST<br />
TIMER SET<br />
TIME<br />
SET CL<br />
FAN<br />
SAVE<br />
SWING/FIX<br />
ON / OFF<br />
MODE<br />
VENT<br />
UNIT LOUVER<br />
2 4 1 3<br />
<br />
1 2 3 4<br />
Returned to usual display<br />
Item code<br />
Data name<br />
Unit<br />
Item code<br />
Data name<br />
Unit<br />
Indoor unit data<br />
01<br />
02<br />
03<br />
04<br />
∗ 07<br />
∗ F2<br />
F3<br />
∗ F8<br />
Room temperature<br />
(Remote controller)<br />
Indoor suction temperature (TA)<br />
Indoor heat exchanger (Coil)<br />
temperature (TCJ)<br />
Indoor heat exchanger (Coil)<br />
temperature (TC)<br />
Indoor fan revolution frequency<br />
Indoor fan calculated operation time<br />
Filter sign time<br />
Indoor discharge temperature*1<br />
°C<br />
°C<br />
°C<br />
°C<br />
rpm<br />
×100h<br />
×1h<br />
°C<br />
Outdoor unit data<br />
60<br />
61<br />
62<br />
63<br />
65<br />
6A<br />
∗ 6D<br />
∗ 70<br />
∗ 72<br />
∗ 73<br />
F1<br />
Outdoor heat exchanger (Coil) temperature (TE)<br />
Outside temperature (TO)<br />
Compressor discharge temperature (TD)<br />
Compressor suction temperature (TS)<br />
Heat sink temperature (THS)<br />
Operation current (× 1/10)<br />
Outdoor heat exchanger (Coil) temperature (TL)<br />
Compressor operation frequency<br />
Outdoor fan revolution frequency (Lower)<br />
Outdoor fan revolution frequency (Upper)<br />
Compressor calculated operation time<br />
°C<br />
°C<br />
°C<br />
°C<br />
°C<br />
A<br />
°C<br />
rps<br />
rpm<br />
rpm<br />
×100h<br />
Items with ∗ marks are not provided to the Slim Duct type.<br />
ò<br />
3 Push UNIT LOUVER button to select the indoor unit to be monitored.<br />
Each data of the indoor unit and its outdoor units can be monitored.<br />
ò<br />
4 Pushing TEST button returns the status to the usual display.<br />
∗1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.<br />
Use this value to check discharge temperature at test run.<br />
(A discharge temperature sensor is not provided to this model.)<br />
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.<br />
• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73]<br />
are not displayed.<br />