12-1-6. Monitor Function of Remote Controller Switch<br />

n Calling of sensor temperature display<br />

<br />

Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor<br />

mode from the remote controller.<br />

<br />

1 Push TEST + CL buttons simultaneously for 4 seconds to<br />

call the service monitor mode.<br />

The service monitor goes on, the master indoor unit No. is<br />

displayed at first and then the temperature of item code 00 is<br />

displayed.<br />

ò<br />

TEMP.<br />

2 Push temperature set buttons and then change<br />

the item code of data to be monitored.<br />

The item code list is shown below.<br />

TEMP.<br />

FILTER<br />

RESET TEST<br />

TIMER SET<br />

TIME<br />

SET CL<br />

FAN<br />

SAVE<br />

SWING/FIX<br />

ON / OFF<br />

MODE<br />

VENT<br />

UNIT LOUVER<br />

2 4 1 3<br />

<br />

1 2 3 4<br />

Returned to usual display<br />

Item code<br />

Data name<br />

Unit<br />

Item code<br />

Data name<br />

Unit<br />

Indoor unit data<br />

01<br />

02<br />

03<br />

04<br />

∗ 07<br />

∗ F2<br />

F3<br />

∗ F8<br />

Room temperature<br />

(Remote controller)<br />

Indoor suction temperature (TA)<br />

Indoor heat exchanger (Coil)<br />

temperature (TCJ)<br />

Indoor heat exchanger (Coil)<br />

temperature (TC)<br />

Indoor fan revolution frequency<br />

Indoor fan calculated operation time<br />

Filter sign time<br />

Indoor discharge temperature*1<br />

°C<br />

°C<br />

°C<br />

°C<br />

rpm<br />

×100h<br />

×1h<br />

°C<br />

Outdoor unit data<br />

60<br />

61<br />

62<br />

63<br />

65<br />

6A<br />

∗ 6D<br />

∗ 70<br />

∗ 72<br />

∗ 73<br />

F1<br />

Outdoor heat exchanger (Coil) temperature (TE)<br />

Outside temperature (TO)<br />

Compressor discharge temperature (TD)<br />

Compressor suction temperature (TS)<br />

Heat sink temperature (THS)<br />

Operation current (× 1/10)<br />

Outdoor heat exchanger (Coil) temperature (TL)<br />

Compressor operation frequency<br />

Outdoor fan revolution frequency (Lower)<br />

Outdoor fan revolution frequency (Upper)<br />

Compressor calculated operation time<br />

°C<br />

°C<br />

°C<br />

°C<br />

°C<br />

A<br />

°C<br />

rps<br />

rpm<br />

rpm<br />

×100h<br />

Items with ∗ marks are not provided to the Slim Duct type.<br />

ò<br />

3 Push UNIT LOUVER button to select the indoor unit to be monitored.<br />

Each data of the indoor unit and its outdoor units can be monitored.<br />

ò<br />

4 Pushing TEST button returns the status to the usual display.<br />

∗1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.<br />

Use this value to check discharge temperature at test run.<br />

(A discharge temperature sensor is not provided to this model.)<br />

• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.<br />

• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73]<br />

are not displayed.<br />