DN<br />

Item<br />

Contents<br />

At shipment from factory<br />

42<br />

Self-clean operation time<br />

0000: None 0000: 0.5 h to 0.012: 0 h<br />

Set when compressor-ON time is 10 to 60 minutes.<br />

When ON-time is 60 minutes or more,<br />

the double of this operation time setting is set.<br />

0002: 1 hour<br />

45<br />

Selection of louver horizontal discharge<br />

position<br />

0000: Smudging-less setting<br />

0002: Cold draft preventive setting<br />

0000: Smudgingless<br />

setting<br />

C2<br />

Current demand X% to outdoor unit<br />

0050: 50% to 0100: 100%<br />

0075: 75%<br />

0000: No<br />

• Clean operation is performed in case of stop by HA input.<br />

CC<br />

Setting of self-clean operation forced stop<br />

• HA operation output OFF during clean operation in case of<br />

stop by remote controller<br />

0001: Yes<br />

0000: None<br />

• Clean operation is not performed in case of stop by HA input.<br />

• HA operation output ON during clean operation in case of stop<br />

by remote controller<br />

CD<br />

Clean operation stop function when<br />

[ON/OFF] operation is prohibited.<br />

The air conditioner stops (including fire alarm such as remote<br />

monitor system) while setup of [ON/OFF] operation prohibited<br />

(Central 1, 2) is performed from the central controller side.<br />

0000: Valid (Clean operation)<br />

0001: Invalid (No clean operation)<br />

0000: Valid<br />

D0<br />

Existence of remote controller save function<br />

0000: Invalid (Impossible) 0001: Valid (Possible)<br />

0001: Valid (Possible)<br />

D1<br />

Existence of 8°C heating operation function<br />

0000: Invalid (Impossible) 0001: Valid (Possible)<br />

0001: Invalid (Impossible)<br />

D3<br />

Revolution frequency of self clean operation<br />

0000: Invalid (Self clean operation is not carried out.)<br />

0001: Valid (Self clean operation is practiced with 210 rpm.)<br />

0001: Valid<br />

(210 rpm / operation)<br />

D4<br />

Display / No display of<br />

[Dry operation] during self clean operation<br />

0000: Display 0001: No display<br />

0000: Display<br />

F0<br />

Louver swing mode<br />

0000: No synchronization 0001: 4-way synchronization<br />

0002: Dual 0003: Cycle<br />

0001: 4-way<br />

synchronization<br />

F1<br />

Louver No.1 fixed position<br />

0000: Release (Free)<br />

0001 to 0005: Horizontal discharge position to<br />

Downward discharge position<br />

0000: Release<br />

F2<br />

Louver No.2 fixed position<br />

0000: Release (Free)<br />

0001 to 0005: Horizontal discharge position to<br />

Downward discharge position<br />

0000: Release<br />

F3<br />

Louver No.3 fixed position<br />

0000: Release (Free)<br />

0001 to 0005: Horizontal discharge position to<br />

Downward discharge position<br />

0000: Release<br />

F4<br />

Louver No.4 fixed position<br />

0000: Release (Free)<br />

0001 to 0005: Horizontal discharge position to<br />

Downward discharge position<br />

0000: Release<br />

∗ The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for<br />

save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).<br />

– 153 –