DN<br />
Item<br />
Contents<br />
At shipment from factory<br />
42<br />
Self-clean operation time<br />
0000: None 0000: 0.5 h to 0.012: 0 h<br />
Set when compressor-ON time is 10 to 60 minutes.<br />
When ON-time is 60 minutes or more,<br />
the double of this operation time setting is set.<br />
0002: 1 hour<br />
45<br />
Selection of louver horizontal discharge<br />
position<br />
0000: Smudging-less setting<br />
0002: Cold draft preventive setting<br />
0000: Smudgingless<br />
setting<br />
C2<br />
Current demand X% to outdoor unit<br />
0050: 50% to 0100: 100%<br />
0075: 75%<br />
0000: No<br />
• Clean operation is performed in case of stop by HA input.<br />
CC<br />
Setting of self-clean operation forced stop<br />
• HA operation output OFF during clean operation in case of<br />
stop by remote controller<br />
0001: Yes<br />
0000: None<br />
• Clean operation is not performed in case of stop by HA input.<br />
• HA operation output ON during clean operation in case of stop<br />
by remote controller<br />
CD<br />
Clean operation stop function when<br />
[ON/OFF] operation is prohibited.<br />
The air conditioner stops (including fire alarm such as remote<br />
monitor system) while setup of [ON/OFF] operation prohibited<br />
(Central 1, 2) is performed from the central controller side.<br />
0000: Valid (Clean operation)<br />
0001: Invalid (No clean operation)<br />
0000: Valid<br />
D0<br />
Existence of remote controller save function<br />
0000: Invalid (Impossible) 0001: Valid (Possible)<br />
0001: Valid (Possible)<br />
D1<br />
Existence of 8°C heating operation function<br />
0000: Invalid (Impossible) 0001: Valid (Possible)<br />
0001: Invalid (Impossible)<br />
D3<br />
Revolution frequency of self clean operation<br />
0000: Invalid (Self clean operation is not carried out.)<br />
0001: Valid (Self clean operation is practiced with 210 rpm.)<br />
0001: Valid<br />
(210 rpm / operation)<br />
D4<br />
Display / No display of<br />
[Dry operation] during self clean operation<br />
0000: Display 0001: No display<br />
0000: Display<br />
F0<br />
Louver swing mode<br />
0000: No synchronization 0001: 4-way synchronization<br />
0002: Dual 0003: Cycle<br />
0001: 4-way<br />
synchronization<br />
F1<br />
Louver No.1 fixed position<br />
0000: Release (Free)<br />
0001 to 0005: Horizontal discharge position to<br />
Downward discharge position<br />
0000: Release<br />
F2<br />
Louver No.2 fixed position<br />
0000: Release (Free)<br />
0001 to 0005: Horizontal discharge position to<br />
Downward discharge position<br />
0000: Release<br />
F3<br />
Louver No.3 fixed position<br />
0000: Release (Free)<br />
0001 to 0005: Horizontal discharge position to<br />
Downward discharge position<br />
0000: Release<br />
F4<br />
Louver No.4 fixed position<br />
0000: Release (Free)<br />
0001 to 0005: Horizontal discharge position to<br />
Downward discharge position<br />
0000: Release<br />
∗ The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for<br />
save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).<br />
– 153 –