(Except 4-way Air Discharge Cassette Type and Under Ceiling Type)<br />

1 Remove a screw which fixes the name plate of the receiver part on the wireless remote<br />

controller.<br />

Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the<br />

bottom of the plate, and set the Dip switch to [TEST RUN ON].<br />

2 Execute a test operation with button on the wireless remote controller.<br />

• , and LED flash during test operation.<br />

• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is<br />

invalid.<br />

Do not use this method in the operation other than test operation because the equipment is damaged.<br />

3 Use either [COOL] or [HEAT] operation mode for test operation.<br />

• The outdoor unit does not operate approx. 3 minutes<br />

after power-ON and operation stop.<br />

4 After the test operation finished, stop the air<br />

conditioner from the wireless remote controller,<br />

and return Dip switch of the sensor section as before.<br />

(A 60 minutes timer clearing function is attached to the sensor<br />

section in order to prevent a continuous test operation.)<br />

M4 × 25 screw<br />

(2 pieces)<br />

Receiver unit<br />

Spacer<br />

Small screw<br />

Notch<br />

Nameplate<br />

(Under Ceiling Type only)<br />

1 Turn off power of the air conditioner.<br />

Remove the adjust corner cap attached with sensor section from the ceiling panel. For removing method,<br />

follow to the installation manual attached to the ceiling panel.<br />

(Be careful to handle the sensor section because cables are connected to the sensor section.)<br />

Remove the sensor cover from the adjust corner cap. (1 screw)<br />

2 Change Bit [1: TEST] of the switch [S003] on the sensor P.C. board from OFF to ON.<br />

Mount the sensor cover and attach the adjust corner cap with with sensors to the ceiling panel.<br />

Turn on power of the air conditioner.<br />

3 Push button of the wireless remote controller and select an operation mode [COOL] or<br />

[HEAT] with MODE<br />

button. (All the display lamps of the wireless remote controller sensor<br />

section flash during the tst operation.)<br />

• Do not use operation mode other than [COOL] or [HEAT].<br />

• Error is detected as usual.<br />

4 When the test operation has finished, push button to stop the operation.<br />

5 Turn off power of the air conditioner.<br />

Change Bit [1] of the switch [S003] on the<br />

sensor P.C. board from ON to OFF.<br />

Attach the adjust corner cap with sensors<br />

to the ceiling panel.<br />

2<br />

3<br />

4<br />

ON<br />

12 3 4<br />