(Except 4-way Air Discharge Cassette Type and Under Ceiling Type)<br />
1 Remove a screw which fixes the name plate of the receiver part on the wireless remote<br />
controller.<br />
Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the<br />
bottom of the plate, and set the Dip switch to [TEST RUN ON].<br />
2 Execute a test operation with button on the wireless remote controller.<br />
• , and LED flash during test operation.<br />
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is<br />
invalid.<br />
Do not use this method in the operation other than test operation because the equipment is damaged.<br />
3 Use either [COOL] or [HEAT] operation mode for test operation.<br />
• The outdoor unit does not operate approx. 3 minutes<br />
after power-ON and operation stop.<br />
4 After the test operation finished, stop the air<br />
conditioner from the wireless remote controller,<br />
and return Dip switch of the sensor section as before.<br />
(A 60 minutes timer clearing function is attached to the sensor<br />
section in order to prevent a continuous test operation.)<br />
M4 × 25 screw<br />
(2 pieces)<br />
Receiver unit<br />
Spacer<br />
Small screw<br />
Notch<br />
Nameplate<br />
(Under Ceiling Type only)<br />
1 Turn off power of the air conditioner.<br />
Remove the adjust corner cap attached with sensor section from the ceiling panel. For removing method,<br />
follow to the installation manual attached to the ceiling panel.<br />
(Be careful to handle the sensor section because cables are connected to the sensor section.)<br />
Remove the sensor cover from the adjust corner cap. (1 screw)<br />
2 Change Bit [1: TEST] of the switch [S003] on the sensor P.C. board from OFF to ON.<br />
Mount the sensor cover and attach the adjust corner cap with with sensors to the ceiling panel.<br />
Turn on power of the air conditioner.<br />
3 Push button of the wireless remote controller and select an operation mode [COOL] or<br />
[HEAT] with MODE<br />
button. (All the display lamps of the wireless remote controller sensor<br />
section flash during the tst operation.)<br />
• Do not use operation mode other than [COOL] or [HEAT].<br />
• Error is detected as usual.<br />
4 When the test operation has finished, push button to stop the operation.<br />
5 Turn off power of the air conditioner.<br />
Change Bit [1] of the switch [S003] on the<br />
sensor P.C. board from ON to OFF.<br />
Attach the adjust corner cap with sensors<br />
to the ceiling panel.<br />
2<br />
3<br />
4<br />
ON<br />
12 3 4<br />
– 148 –