12-1. Indoor Unit<br />

12. SETUP AT LOCAL SITE AND OTHERS<br />

12-1-1. Test Run Setup on Remote Controller<br />

<br />

1. When pushing TEST button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.<br />

ON / OFF<br />

Then push button.<br />

• “TEST” is displayed on LC display during operation of Test Run.<br />

• During Test Run, temperature cannot be adjusted but air volume can be selected.<br />

• In heating and cooling operation, a command to fix the Test Run frequency is output.<br />

• Detection of error is performed as usual. However, do not use this function except case of Test Run<br />

because it applies load on the unit.<br />

2. Use either heating or cooling operation mode for [TEST].<br />

NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after<br />

operation has stopped.<br />

3. After a Test Run has finished, push TEST button again and check that [TEST] on LC display has gone off.<br />

(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote<br />

controller.)<br />

<br />

(4-way Air Discharge Cassette Type only)<br />

1 Turn off power of the unit.<br />

Remove the adjuster attached with sensors from the ceiling panel.<br />

For removing, refer to the Installation manual attached to the ceiling panel.<br />

(Be careful to handle the adjuster because cables are connected to the sensor.)<br />

Remove the sensor cover from the adjuster. (1 screw)<br />

2 Change ON of Bit [1: TEST] of the sensor P.C. board switch [S003] to OFF.<br />

Mount the sensor cover and mount the adjuster with sensor to the ceiling panel.<br />

Turn on power of the unit.<br />

ON / OFF<br />

3 Push button on the wireless remote controller and select [COOL] or [HEAT] operation<br />

mode using MODE<br />

button.<br />

(All the display lamps of sensors on the wireless remote controller flash during Test Run.)<br />

• Do not perform Test Run operation in other modes than [HEAT] / [COOL] mode.<br />

• Detection of error is performed as usual.<br />

4 After Test Run operation, push<br />

ON / OFF<br />

button to stop the operation.<br />

5 Turn off power of the unit.<br />

Return Bit [1] of the sensor P.C. board switch [S003]<br />

to the original position. (ON → OFF)<br />

Mount the adjuster with sensors to the ceiling panel.<br />

DIP switch S003<br />

Bit 1: OFF → ON<br />

ON<br />

1<br />

2<br />

3<br />

4<br />

Sensor cover<br />

Sensor board<br />

Adjust corner cap<br />

with sensor<br />