Revised 2: Jun., 2008<br />

Table 1. Setting data (CODE No. table (example))<br />

DN<br />

Item<br />

Setting data<br />

Factory-set value<br />

01<br />

Filter sign lighting time<br />

Depending on Type<br />

02<br />

Filter pollution leve<br />

0000: standard<br />

03<br />

Central control address<br />

0099: Not determined<br />

06<br />

Heating suction temperature shift<br />

0002: +2°C<br />

(flooring installation type: 0)<br />

OF<br />

Cooling only<br />

0000: Heat pump<br />

10<br />

Type<br />

Depending on model type<br />

11<br />

Indoor unit capacity<br />

Depending on capacity type<br />

12<br />

System address<br />

0099: Not determined<br />

13<br />

Indoor unit address<br />

0099: Not determined<br />

14<br />

Group address<br />

0099: Not determined<br />

19<br />

Louver type (wind direction adjustment)<br />

Depending on Type.<br />

1E<br />

Temperature range of cooling/heating<br />

automatic SW control point<br />

0003: 3 deg (Ts ± 1.5)<br />

28<br />

Power failure automatic recovery<br />

0000: None<br />

2A<br />

Option/Abnormal input (CN70) SW<br />

0002: Humidifier<br />

2b<br />

Thermo output SW (T10 ƒ )<br />

0000: Thermo ON<br />

31<br />

Ventilation fan (standalone)<br />

0000: Not available<br />

32<br />

Sensor SW (Selection of static pressure)<br />

0000: Body sensor<br />

40<br />

Humidifier control (+ drain pump control)<br />

0003: Humidifier ON + Pump OFF<br />

5d<br />

High ceiling SW<br />

0000: Standard<br />

60<br />

Timer setting (wired remote controller)<br />

0000: Available<br />

C2<br />

Demand setting<br />

(outdoor unit current demand)<br />

0075: 75 %<br />

d0<br />

Remote controller operation save function<br />

0001: Enable<br />

d3<br />

Rotation number of the self-clean operation<br />

0001: 210ypm(at self-clean operation)<br />

d1<br />

Frost protection function<br />

0000: None<br />

F0<br />

Swing mode<br />

0001: Standard<br />

F1<br />

Louver fixing position (Flap No. 1)<br />

0000: Not fixed<br />

F2<br />

Louver fixing position (Flap No. 2)<br />

0000: Not fixed<br />

F3<br />

Louver fixing position (Flap No. 3)<br />

0000: Not fixed<br />

F4<br />

Louver fixing position (Flap No. 4)<br />

0000: Not fixed<br />

Table 2. Type: CODE No. 10<br />

Table 3.<br />

Indoor unit capacity: CODE No. 11<br />

Setting data<br />

0001 *1 * 2<br />

0005<br />

Type<br />

4-way Air Discharge Cassette Type<br />

Slim Duct Type<br />

Type name abb.<br />

RAV-SM∗∗∗UT-E<br />

RAV-SM∗∗∗SDT-E<br />

∗1 EEPROM initial value on the P.C. board for indoor unit servicing<br />

∗2<br />

CAUTION<br />

<br />

For the above models, set the CODE No. to “ CE ” and the setting<br />

data 0000 (initial) to “0001”.<br />

Setting data<br />

0000∗<br />

0006<br />

0007<br />

0009<br />

0012<br />

0015<br />

0017<br />

0018<br />

Type<br />

Disable<br />

40<br />

45<br />

56<br />

80<br />

110<br />

140<br />

160<br />

∗ EEPROM initial value on the P.C. board<br />

for indoor unit servicing.<br />

– 145 –