Step 4 Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2<br />
above again.<br />
Step 5 Change the CODE No. (DN) to “01 ” by pushing / buttons for the temperature setting.<br />
(this is the setting for the filter sign lighting time.)<br />
Step 6 Check the setting data displayed at this time with the setting data put down in [1].<br />
1. If the setting data is different, modify the setting data by pushing / buttons for the timer setting to<br />
the data put down in [1].<br />
The operation completes if the setting data is displayed.<br />
2. If the data is the same, proceed to next step.<br />
Step 7 Change the CODE No. (DN) by pushing / buttons for the temperature setting.<br />
As described above, check the setting data and modify to the data put down in [1].<br />
Step 8 Repeat the steps 6 and 7.<br />
Step 9 After the setting completes, push TEST button to return to the normal stop status.<br />
(It takes approx. 1 min until the remote control operation is available again.)<br />
∗ The CODE No. (DN) are ranged from “01 ” to “FF ”. The CODE No. (DN) is not limited to be serial No.<br />
Even after modifying the data wrongly and pushing SET<br />
button, it is possible to return to the data before<br />
modification by pushing CL<br />
button if the CODE No. (DN) is not changed.<br />
<br />
The EEPROM (IC503) is attached to the IC socket. When detaching the EEPROM, use a tweezers, etc.<br />
Be sure to attach the EEPROM by fitting its direction as shown in the figure.<br />
∗ Do not bend the IC lead when replacing.<br />
Cut out<br />
EEPROM<br />
EEPROM<br />
IC503<br />
Cut out<br />
IC socket<br />
– 144 –