Revised 2: Jun., 2008<br />
Setting 4-way air discharge cassette Indoor Unit model only<br />
1. Using the set temperature / buttons, set “CE ” to the CODE No. (DN).<br />
2. Using the timer time / buttons, set the data. (0001)<br />
• Push SET<br />
button. (The setting completes if the setting data are displayed.)<br />
<br />
Connector (CN504)<br />
for drain pump<br />
If the plug for short-circuit is attached on the P.C. board<br />
before replacement, attach it on the P.C. board replaced.<br />
CN34<br />
(Red)<br />
J01<br />
SW501<br />
J02<br />
CAUTION<br />
Be sure to set the jumper wire since the motor<br />
protection level setting selection is performed on it.<br />
∗ Set J02 as follows depending on the capacity class.<br />
Type<br />
4-Way<br />
Air Discharge Cassette<br />
Slim Duct<br />
SM56, 80<br />
SM110, 140, 160<br />
SM40 to 56<br />
Jumper wire (J02)<br />
None<br />
Required (factory setting)<br />
None<br />
<br />
• As P.C. board of the Slim Duct type differs from that of the 4-way Discharge Cassette type, selection by HP is<br />
unnecessary.<br />
• Push the TEST<br />
button to return to the normal stop status.<br />
(It takes approx. 1 min until the remote controller operation is available again.)<br />
[3] Writing the setting data to EEPROM<br />
The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.<br />
Step 1 Push SET , CL and TEST buttons on the remote controller simultaneously for more than 4 seconds.<br />
∗ In the group control operation, the unit No. displayed for the first time is the header unit No.<br />
At this time, the CODE No. (DN) shows “10 ”. Also, the fan of the indoor unit selected starts its operation<br />
and the swing operation starts if it has the louvers.<br />
(The unit No. “ ” is displayed if the auto-address setting mode is interrupted in [2] step 2 a))<br />
Step 2 Every time when UNIT LOUVER button is pushed, the indoor unit No. in the group control operation are displayed<br />
in order.<br />
(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)<br />
Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing.<br />
(You cannot perform this operation if “ ” is displayed.)<br />
Step 3 Select the CODE No. (DN) can be selected by pushing the / button for the temperature setting.<br />
• Set the indoor unit type and capacity.<br />
The factory-set values shall be written to the EEPROM by changing <br />
the type and capacity.<br />
1. Set the CODE No. (DN) to “10 ”. (without change)<br />
2. Select the type by pushing / buttons for the timer setting.<br />
(For example, 4-way Air Discharge Cassette Type is set to “0001”.<br />
Refer to table 2)<br />
3. Push SET button.<br />
(The operation completes if the setting data is displayed.)<br />
4. Change the CODE No. (DN) to “11 ” by pushing /<br />
buttons for the temperature setting.<br />
5. Select the capacity by pushing / buttons for the timer setting.<br />
(For example, 80 Type is set to “0012”. Refer to table 3)<br />
6. Push SET button.<br />
(The setting completes if the setting data are displayed.)<br />
– 143 –<br />