Revised 2: Jun., 2008<br />

Setting 4-way air discharge cassette Indoor Unit model only<br />

1. Using the set temperature / buttons, set “CE ” to the CODE No. (DN).<br />

2. Using the timer time / buttons, set the data. (0001)<br />

• Push SET<br />

button. (The setting completes if the setting data are displayed.)<br />

<br />

Connector (CN504)<br />

for drain pump<br />

If the plug for short-circuit is attached on the P.C. board<br />

before replacement, attach it on the P.C. board replaced.<br />

CN34<br />

(Red)<br />

J01<br />

SW501<br />

J02<br />

CAUTION<br />

Be sure to set the jumper wire since the motor<br />

protection level setting selection is performed on it.<br />

∗ Set J02 as follows depending on the capacity class.<br />

Type<br />

4-Way<br />

Air Discharge Cassette<br />

Slim Duct<br />

SM56, 80<br />

SM110, 140, 160<br />

SM40 to 56<br />

Jumper wire (J02)<br />

None<br />

Required (factory setting)<br />

None<br />

<br />

• As P.C. board of the Slim Duct type differs from that of the 4-way Discharge Cassette type, selection by HP is<br />

unnecessary.<br />

• Push the TEST<br />

button to return to the normal stop status.<br />

(It takes approx. 1 min until the remote controller operation is available again.)<br />

[3] Writing the setting data to EEPROM<br />

The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.<br />

Step 1 Push SET , CL and TEST buttons on the remote controller simultaneously for more than 4 seconds.<br />

∗ In the group control operation, the unit No. displayed for the first time is the header unit No.<br />

At this time, the CODE No. (DN) shows “10 ”. Also, the fan of the indoor unit selected starts its operation<br />

and the swing operation starts if it has the louvers.<br />

(The unit No. “ ” is displayed if the auto-address setting mode is interrupted in [2] step 2 a))<br />

Step 2 Every time when UNIT LOUVER button is pushed, the indoor unit No. in the group control operation are displayed<br />

in order.<br />

(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)<br />

Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing.<br />

(You cannot perform this operation if “ ” is displayed.)<br />

Step 3 Select the CODE No. (DN) can be selected by pushing the / button for the temperature setting.<br />

• Set the indoor unit type and capacity.<br />

The factory-set values shall be written to the EEPROM by changing <br />

the type and capacity.<br />

1. Set the CODE No. (DN) to “10 ”. (without change)<br />

2. Select the type by pushing / buttons for the timer setting.<br />

(For example, 4-way Air Discharge Cassette Type is set to “0001”.<br />

Refer to table 2)<br />

3. Push SET button.<br />

(The operation completes if the setting data is displayed.)<br />

4. Change the CODE No. (DN) to “11 ” by pushing /<br />

buttons for the temperature setting.<br />

5. Select the capacity by pushing / buttons for the timer setting.<br />

(For example, 80 Type is set to “0012”. Refer to table 3)<br />

6. Push SET button.<br />

(The setting completes if the setting data are displayed.)<br />

– 143 –<br />

3651 42