[C06 error] (TCC-LINK central controller)<br />
<br />
Are U3 and U4 communication lines normal?<br />
YES<br />
NO<br />
Correct communication line.<br />
∗1<br />
Is connection of connector normal?<br />
NO<br />
Correct connection of connector.<br />
YES<br />
∗1<br />
TCC-LINK central:<br />
CN51 of TCC-LINK adapter P.C. board (MCC-1440) and CN050 of indoor P.C. board<br />
Are A and B communication lines normal?<br />
YES<br />
Is there no connection error of power supply cable?<br />
NO<br />
Is not the source power supply turned on?<br />
YES<br />
Did a power failure occur?<br />
NO<br />
NO<br />
YES<br />
NO<br />
YES<br />
Check connection of A and B terminal blocks.<br />
Correct communication line of remote controller.<br />
Correct power wiring.<br />
Turn on the source power supply.<br />
Is the network address changed<br />
from the remote controller?<br />
NO<br />
Is there no noise source?<br />
NO<br />
YES<br />
YES<br />
Clear the check code.<br />
Eliminate noise, etc.<br />
Can the other indoor units<br />
be normally controlled from the central controller?<br />
Or is the operation status of indoor unit reflected?<br />
Uncontrolled<br />
(Same to others)<br />
Check central controller.<br />
Defect → Replace<br />
YES<br />
Can the indoor unit be normally controlled<br />
from the remote controller?<br />
YES<br />
Uncontrolled<br />
Check indoor P.C. board (MCC-1570).<br />
Defect → Replace<br />
Check power supply transformer on<br />
TCC-LINK adapter P.C. board (MCC-1440).<br />
Defect → Replace<br />