[C06 error] (TCC-LINK central controller)<br />

<br />

Are U3 and U4 communication lines normal?<br />

YES<br />

NO<br />

Correct communication line.<br />

∗1<br />

Is connection of connector normal?<br />

NO<br />

Correct connection of connector.<br />

YES<br />

∗1<br />

TCC-LINK central:<br />

CN51 of TCC-LINK adapter P.C. board (MCC-1440) and CN050 of indoor P.C. board<br />

Are A and B communication lines normal?<br />

YES<br />

Is there no connection error of power supply cable?<br />

NO<br />

Is not the source power supply turned on?<br />

YES<br />

Did a power failure occur?<br />

NO<br />

NO<br />

YES<br />

NO<br />

YES<br />

Check connection of A and B terminal blocks.<br />

Correct communication line of remote controller.<br />

Correct power wiring.<br />

Turn on the source power supply.<br />

Is the network address changed<br />

from the remote controller?<br />

NO<br />

Is there no noise source?<br />

NO<br />

YES<br />

YES<br />

Clear the check code.<br />

Eliminate noise, etc.<br />

Can the other indoor units<br />

be normally controlled from the central controller?<br />

Or is the operation status of indoor unit reflected?<br />

Uncontrolled<br />

(Same to others)<br />

Check central controller.<br />

Defect → Replace<br />

YES<br />

Can the indoor unit be normally controlled<br />

from the remote controller?<br />

YES<br />

Uncontrolled<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

Check power supply transformer on<br />

TCC-LINK adapter P.C. board (MCC-1440).<br />

Defect → Replace<br />