[F02 error]<br />

Revised 2: Jun., 2008<br />

Is connection of TC sensor connector<br />

(CN101 on Indoor P.C. board) correct?<br />

YES<br />

NO<br />

Correct connection of connector.<br />

Are characteristics of<br />

TC sensor resistance value normal?<br />

NO<br />

Replace TC sensor.<br />

YES<br />

∗ Refer to TC sensor<br />

(Temperature-Resistance value characteristic table)<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

[F01 error]<br />

Is connection of TCJ sensor connector<br />

(CN102 on Indoor P.C. board) correct?<br />

YES<br />

NO<br />

Correct connection of connector.<br />

Are characteristics of<br />

TCJ sensor resistance value normal?<br />

NO<br />

Replace TCJ sensor.<br />

YES<br />

∗ Refer to Characteristics-2.<br />

Check indoor main P.C. board (MCC-1570).<br />

Defect → Replace<br />