[L20 error] Are wiring connections to communication lines U3 and U4 normal? YES NO Correct wiring connection. Is not the multiple same central control system addresses connected? NO YES Correct central control system address. Check central controller (including network adapter) and indoor P.C. board (MCC-1570). Defect → Replace [L30 error] Are outside devices of connector CN80 connected? YES Do outside devices normally work? YES NO NO Check indoor P.C. board (MCC-1570). Defect → Replace Check outside devices. Defect → Replace Check cause of operation. [P30 error] (Central controller) Is group operation carried out? YES NO Is there check code on sub remote controller in main and sub remote controllers? YES NO Check corresponding indoor unit/outdoor unit. Check indoor P.C. board (MCC-1570). Defect → Replace – 130 –

[P10 error] Revised 2: Jun., 2008 Is connection of float switch connector (Indoor control board CN34) normal? YES NO Correct connection of connector. Does float switch work? NO Is circuit wiring normal? YES YES NO Check and correct wiring and wire circuit. Does drain pump work? NO YES Is power of drain pump turned on? ∗ NO Are connector pins 1 and 2 at drain pump unit side shorted (Resistance value 0)? NO YES YES Check the drain pipe, etc. Replace drain pump and indoor P.C. board (MCC-1570). Replace drain pump. Check wiring. Check indoor P.C. board (MCC-1570). Defect → Replace ∗ Check that voltage of 1-2 pin of CN504 on the indoor P.C. board is +12V. (1 pin is plus (+).) [F10 error] Is connection of TA sensor connector (CN104 on indoor P.C. board) correct? YES NO Correct connection of connector. Are characteristics of TA sensor resistance value normal? NO Replace TA sensor. YES ∗ Refer to TA sensor (Temperature-Resistance value characteristic table) Check indoor P.C. board (MCC-1570). Defect → Replace – 131 –

[P10 error]<br />

Revised 2: Jun., 2008<br />

Is connection of<br />

float switch connector<br />

(Indoor control board CN34)<br />

normal?<br />

YES<br />

NO<br />

Correct connection<br />

of connector.<br />

Does float switch work?<br />

NO<br />

Is circuit wiring normal?<br />

YES<br />

YES<br />

NO<br />

Check and correct wiring<br />

and wire circuit.<br />

Does drain pump work?<br />

NO<br />

YES<br />

Is power of<br />

drain pump turned on? ∗<br />

NO<br />

Are connector pins 1 and 2<br />

at drain pump unit side shorted<br />

(Resistance value 0)?<br />

NO<br />

YES<br />

YES<br />

Check the drain pipe, etc.<br />

Replace drain pump<br />

and indoor P.C. board<br />

(MCC-1570).<br />

Replace drain pump.<br />

Check wiring.<br />

Check indoor P.C. board<br />

(MCC-1570).<br />

Defect → Replace<br />

∗ Check that voltage of 1-2 pin of CN504 on the indoor P.C. board is +12V. (1 pin is plus (+).)<br />

[F10 error]<br />

Is connection of TA sensor connector<br />

(CN104 on indoor P.C. board) correct?<br />

YES<br />

NO<br />

Correct connection of connector.<br />

Are characteristics of<br />

TA sensor resistance value normal?<br />

NO<br />

Replace TA sensor.<br />

YES<br />

∗ Refer to TA sensor<br />

(Temperature-Resistance value characteristic table)<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

– 131 –