[L20 error]<br />

<br />

Are wiring connections<br />

to communication lines<br />

U3 and U4 normal?<br />

YES<br />

NO<br />

Correct wiring connection.<br />

Is not the multiple same central<br />

control system addresses connected?<br />

NO<br />

YES<br />

Correct central control system address.<br />

Check central controller<br />

(including network adapter) and<br />

indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

[L30 error]<br />

Are outside devices of<br />

connector CN80 connected?<br />

YES<br />

Do outside devices normally work?<br />

YES<br />

NO<br />

NO<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

Check outside devices.<br />

Defect → Replace<br />

Check cause of operation.<br />

[P30 error] (Central controller)<br />

Is group operation carried out?<br />

YES<br />

NO<br />

Is there check code<br />

on sub remote controller in main<br />

and sub remote controllers?<br />

YES<br />

NO<br />

Check corresponding<br />

indoor unit/outdoor unit.<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />