10-2-9. Diagnostic Procedure for Each Check Code (Indoor Unit)<br />

<br />

Check code<br />

[E01 error]<br />

Is inter-unit cable of A and B normal?<br />

YES<br />

NO<br />

Correct inter-unit cable<br />

of remote controller<br />

Is there no disconnection or<br />

contact error of connector on harness<br />

from terminal block of indoor unit?<br />

NO<br />

YES<br />

Correct connection of connector.<br />

Check circuit wiring.<br />

NO<br />

Is group control operation?<br />

YES<br />

Is power of all indoor units turned on?<br />

YES<br />

NO<br />

Check power connection of indoor unit.<br />

(Turn on power again.)<br />

Is power supplied to remote controller?<br />

AB terminal: Approx. DC18V<br />

YES<br />

NO<br />

Check indoor P.C. board (MCC-1570).<br />

Defect → Replace<br />

Are 2 remote controllers set<br />

without master unit?<br />

NO<br />

YES<br />

Correct a master unit/a follower unit.<br />

(Remote controller address connector)<br />

Check remote controller P.C. board.<br />

Defect → Replace<br />

[E09 error]<br />

Are 2 master units set in<br />

2 remote controllers?<br />

NO<br />

YES<br />

Correct as a master unit<br />

and a follower unit.<br />

Check remote controller P.C. board.<br />

Defect → Replace<br />