Lamp indication<br />

Check code<br />

Cause of trouble occurrence<br />

<br />

Operation Timer Ready<br />

Alternate flash<br />

F01<br />

F02<br />

P10<br />

Heat exchanger sensor (TCJ) error<br />

Heat exchanger sensor (TC) error<br />

Heat exchanger sensor (TA) error<br />

⎫<br />

⎪<br />

⎬<br />

⎪<br />

⎭<br />

Indoor unit sensor error<br />

Operation Timer Ready<br />

Alternate flash<br />

F04<br />

F06<br />

F08<br />

F12<br />

Discharge temp. sensor (TD) error<br />

Temp. sensor (TE) error<br />

Temp. sensor (TO) error<br />

Temp. sensor (TS) error<br />

⎫<br />

⎪<br />

⎪<br />

⎬<br />

⎪<br />

⎪<br />

⎭<br />

Sensor error of outdoor unit ∗1<br />

Operation Timer Ready<br />

F29<br />

Indoor EEPROM error<br />

Simultaneous flash<br />

Operation Timer Ready<br />

Flash<br />

Operation Timer Ready<br />

Simultaneous flash<br />

H01<br />

H02<br />

H03<br />

L03<br />

L07<br />

L08<br />

L09<br />

⎫<br />

Compressor break down ⎪<br />

Compressor lock ⎬ Outdoor compressor system error ∗1<br />

⎪<br />

Current detection circuit error ⎭<br />

Duplicated master indoor units ⎫<br />

⎪<br />

There is indoor unit of group connection<br />

⎬<br />

→ AUTO address<br />

in individual indoor unit.<br />

⎪ * If group construction and<br />

Unsetting of group address<br />

⎭ address are not normal<br />

Missed setting<br />

when power supply turned on,<br />

(Unset indoor capacity)<br />

automatically goes to address<br />

setup mode.<br />

Operation Timer<br />

Simultaneous flash<br />

Ready<br />

L20<br />

L30<br />

L31<br />

Duplicated indoor central addresses<br />

Outside interlock error<br />

Negative phase error<br />

⎫<br />

⎪<br />

⎬<br />

⎪<br />

⎭<br />

Others<br />

∗1: These are representative examples and the check code differs according to the outdoor unit to be combined.<br />

10-2-7. Others (Other than Check Code)<br />

Lamp indication<br />

Operation Timer Ready<br />

Check code<br />

Cause of trouble occurrence<br />

—<br />

During test run<br />

Simultaneous flash<br />

Operation Timer Ready<br />

Alternate flash<br />

—<br />

Disagreement of cool/heat<br />

(Automatic cool/heat setting to automatic cool/heat prohibited model, or<br />

setting of heating to cooling-only model)<br />