SUPER DIGITAL
SUPER DIGITAL
SUPER DIGITAL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Check<br />
code<br />
Outdoor<br />
LED display<br />
<br />
Check and troubleshooting<br />
(Item without special mention Indicates part of outdoor unit.)<br />
[P07]<br />
<br />
¡ ¥<br />
¡ ¥<br />
¡ ¥<br />
l l<br />
¡ l<br />
¡ ¡<br />
[Heat sink overheat error]<br />
Is there no loosening of<br />
screws of motor drive element of<br />
outdoor P.C. board Q200, Q300, Q400<br />
and rectifier DB01, DB02, DB03?<br />
Did not forget to apply<br />
radiation grease to rear side of<br />
Q200, DB01, DB02 or DB03?<br />
YES<br />
NO<br />
Apply radiation grease to objective part.<br />
Retightening of screws.<br />
(Be sure not to forget to attach insulating sheet<br />
between heat sink and Q300, Q400.)<br />
Is not the ventilation flue<br />
of the heat sink blocked?<br />
Is not the fan blocked?<br />
(Short-circuit, etc.)<br />
NO<br />
Remove blocking matter.<br />
Correct short-circuit.<br />
YES<br />
Check outdoor P.C. board.<br />
Defect → Replace<br />
[P15]<br />
<br />
¡ ¥<br />
¡ ¥<br />
¡ ¥<br />
l ¥<br />
¡ l<br />
¡ ¡<br />
[Gas leak detection]<br />
Is there no gas leak?<br />
Is refrigerant charge amount adequate?<br />
YES<br />
Is PMV normal?<br />
NO<br />
NO<br />
Repair defective position.<br />
Recharge refrigerant.<br />
Correct defective position.<br />
Replace defective part.<br />
YES<br />
Is valve fully opened?<br />
NO<br />
Open valve fully.<br />
YES<br />
Is there no crushed pipe?<br />
YES<br />
Correct and replace piping.<br />
NO<br />
Check temp. sensor.<br />
TD sensor CN603<br />
TS sensor CN600<br />
Error<br />
Correct connector.<br />
Sensor error → Replace<br />
OK<br />
Check outdoor P.C. board.<br />
Defect → Replace<br />
– 115 –