10-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)<br />

<br />

1) This section describes the diagnostic method for each check code displayed on the remote controller.<br />

2) In some cases, a check code indicates multiple symptoms.<br />

In this case, confirm LED display on the outdoor P.C. board to narrow the contents to be confirmed.<br />

3) The check code on the remote controller is displayed only when the same error occurred continuously by<br />

multiple times while LED of the outdoor P.C. board displays even an error which occurred once.<br />

Therefore the display on the remote controller may differ from that of LED.<br />

LED display on outdoor P.C. board<br />

Dip switch setup<br />

• When turning on 1) only of SW803, the latest error<br />

is displayed. As the memory is stored, it can be<br />

confirmed even if the power supply is turned off<br />

once. (excluding outside temp. sensor (TO) error)<br />

• When the work finished or the outdoor temp.<br />

sensor (TO) error was found, turn off all of SW803.<br />

(The error which occurs at present is displayed.)<br />

<br />

Only 1) of SW803 is ON.<br />

ON<br />

<br />

All SW803 are OFF. (Initial status)<br />

ON<br />

1 2 3 4<br />

1 2 3 4<br />

Display selection<br />

• When even a LED of D800 to D804 (Yellow)<br />

goes on, error occurrence is indicated. <br />

• If pushing the button switch SW800 for 1 second<br />

under the above condition, the yellow LED is<br />

displayed with flashing. <br />

• When pushing SW800 for 1 second again, the<br />

status returns to .<br />

• The error contents can be confirmed by combining<br />

and .<br />

(No error)<br />

ó <br />

(Error occurred) (Push SW800)<br />

D800 (Yellow) l ¡ l<br />

D801 (Yellow) l ¡ l<br />

D802 (Yellow) l l ¥<br />

D803 (Yellow) l l l<br />

D804 (Yellow) l ¡ l<br />

D805 (Green) ¡ ¡ ¡<br />

(Example of discharge temp. sensor error)<br />

l : Go off, ¡ : Go on, ¥ : Flash<br />

Check<br />

code<br />

[E04]<br />

Outdoor<br />

LED display<br />

—<br />

Check and troubleshooting<br />

(Item without special mention Indicates part of outdoor unit.)<br />

[Indoor/Outdoor communication error]<br />

Is setting of group address<br />

of remote controller correct?<br />

YES<br />

Are inner wiring and<br />

inter-unit cables (1, 2, 3) normal?<br />

YES<br />

Are CN04 connection and<br />

wiring of terminal blocks (1, 2, 3) normal?<br />

YES<br />

Does D502 (Orange LED) flash after<br />

power supply is turned on again?<br />

YES<br />

NO<br />

NO<br />

NO<br />

NO<br />

Check Item code [14].<br />

Correct wiring<br />

and inter-unit cable.<br />

Correct wiring of connectors<br />

and terminal blocks.<br />

Check indoor P.C. board.<br />

Defect → Replace<br />

Check outdoor P.C. board.<br />

Defect → Replace<br />