Electrical Specifications<br />
(3+3) Electrical System<br />
Dividends Horizon<br />
3+3 Electrical System<br />
The Dividends Horizon 3+3 electrical system<br />
is designed for areas where power usage is<br />
<br />
<br />
The wiring configuration of the 3+3<br />
electrical system is (see chart):<br />
<br />
<br />
<br />
<br />
circuits #1, 2 and 3<br />
<br />
circuits #1, 2 and 3<br />
<br />
<br />
<br />
<br />
circuits 4, 5 and 6<br />
<br />
for circuits 4, 5 and 6<br />
Circuits 1, 2 and 3 are for convenience<br />
power while circuits 4, 5 and 6 are for<br />
designated/ isolated power or for supporting<br />
uninterrupted power supply (UPS).<br />
Compatibility<br />
All Dividends Horizon power systems<br />
use components that appear similar.<br />
However, components from the three<br />
different power systems are not functionally,<br />
fully interchangeable. 3+3 components<br />
can be connected to 3+1 systems,<br />
however only 8-wires will function.<br />
Wiring Diagram (3+3)<br />
Circuits<br />
1 2 3 4 5 6<br />
Wires<br />
Black<br />
Red<br />
Blue<br />
A<br />
B<br />
C<br />
3+3 Duplex Receptacles<br />
Duplex receptacles used in 3+3<br />
electrical systems are:<br />
<br />
1(pattern number DE1DR1)<br />
<br />
2 (pattern number DE1DR2)<br />
<br />
3 (pattern number DE1DR3)<br />
<br />
(pattern number DE1DR4)<br />
<br />
(pattern number DE1DR5)<br />
<br />
(pattern number DE1DR6)<br />
Isolated duplex receptacles number 4, 5 and<br />
6 have an orange-colored triangle on black<br />
background to signify as an isolated duplex.<br />
Optional orange-colored isolated duplexes<br />
are also available. They have the isolated<br />
identifying triangle outlined in black.<br />
<br />
number 4 (pattern number DE1DOR4)<br />
<br />
number 5 (pattern number DE1DOR5)<br />
<br />
number 6 (pattern number DE1DOR6)<br />
Z<br />
Y<br />
X<br />
Wires<br />
Orange<br />
Tan<br />
Pink<br />
3+3 Electrical System Technical<br />
Specifications<br />
The 3+3 electrical system consists of six 20<br />
amp, 120 volt, 60-Hertz circuits. The circuits<br />
will accommodate 120 volt single phase,<br />
120/240 volt split phase and 120/208 volt three<br />
phase power. System components are 20 amp<br />
capacity. The National Electric Code (NEC)<br />
limits continuous loads to 80% of capacity or<br />
16 amps. Typically, each circuit can power 8-10<br />
duplex convenience outlets with normal loads.<br />
In heavier load situations, such as computer<br />
systems, each circuit will power 3-5 duplex<br />
outlets. If each workstation has two convenience<br />
duplex outlets and one protected duplex, the<br />
10-wire (6-circuit) system can supply a cluster<br />
of 9 -15 workstations from each infeed.<br />
Surge Suppressors<br />
Dividends Horizon surge suppressors<br />
(pattern number DE1SS) plug into any<br />
terminal block position to provide surge<br />
protection for all duplexes on that circuit.<br />
Note: When connected, surge suppressors take<br />
the place of a duplex receptacle resulting in the<br />
elimination of one duplex position from the circuit.<br />
Independent Neutral Electrical Systems<br />
Dividends Horizon offers a 10-wire/2+2 electrical<br />
system with independent neutrals as a standard<br />
special. It is our belief that independent neutrals<br />
<br />
an independent neutral electrical system, a<br />
Dividends Horizon solution can be provided. For<br />
further information, list pricing and schematic<br />
drawings, contact <strong>Knoll</strong> Customer Service.<br />
SPECIFYING ELECTRICAL COMPONENTS<br />
Panel Power Module<br />
Specify one panel power module per<br />
panel that matches the width of the panel<br />
<br />
Power Connector<br />
Specify one power connector (with or<br />
without post) to connect panel power<br />
modules in adjacent panels.<br />
Power Jumper<br />
Specify one power jumper that matches<br />
the width of the panel(s) being passed<br />
through to connect to panel power<br />
modules in nonadjacent panels.<br />
White/<br />
Black<br />
N1<br />
N2<br />
White/<br />
Red<br />
Green<br />
G1<br />
G2<br />
Green/<br />
Yellow<br />
180