Note:<br />
When the cache mode is enabled, all the read data will be read from <strong>IFD9506</strong>. In this way, the read<br />
speed can be enhanced.<br />
10.6 Application of Modbus Slave<br />
Application<br />
Steps<br />
Giving Modbus command from HMI to remote device.<br />
(1) HMI sends out the instruction.<br />
(2) Set the IP of slave <strong>IFD9506</strong> to “192.168.1.6”, station address to “7” and communication<br />
format to “38400, 8, E, 1, RTU”.<br />
(3) In the <strong>IFD9506</strong> serial slave mode table, set the device address to “1” and “3”, the two<br />
relay IPs to “192.168.1.5”.<br />
(4) Set the IP of master of <strong>IFD9506</strong> to “192.168.1.5", station address to “8” and<br />
communication format to “38400, 8, E, 1, RTU”.<br />
(5) HMI master and <strong>IFD9506</strong> slave transmit data through RS-485.<br />
(6) <strong>IFD9506</strong> slave and <strong>IFD9506</strong> master transmit data through <strong>Ethernet</strong>.<br />
(7) The RS-485 terminal on <strong>IFD9506</strong> master is connected to two devices, which are PLC at<br />
station address 0x0001 and PLC at station address 0x0003. Assume the communication<br />
format is “38400, 8, E, 1, RTU”.<br />
1. The wiring:<br />
44<br />